18.0)

LIGHTING AND SHUTDOWN INSTRUCTIONS

1. Turn on the gas and electrical supply. Rotate the gas valve knob counter-clockwise
2. Set the thermostat to call for heat. The blower motor will energize.
3. Ignition should occur after the 15-second pre-purge.
4. If the burner fails to light, or flame is not detected during the first trial for ignition (a period of approximately
15 seconds) the gas valve is de-energized and the control goes through an inter-purge delay of
approximately 60 seconds before another ignition attempt. The control will attempt two additional ignition
trials before going into lockout, and the valve relay will be de-energized immediately. The blower will be
turned off following a post-purge period of approximately 30 seconds.
5. If the heater does not light, manually reset the thermostat or shut off power completely for 5 minutes before
attempting to relight.
6. To permanently shut down the heater, rotate the gas valve knob clockwise
off the gas and electrical supply.
NOTE: T
NOTE: T
NOTE: T
NOTE: The lighting and shutdown instructions are als
he lighting and shutdown instructions are als
he lighting and shutdown instructions are also shown on the permanent nameplate label attached to the
he lighting and shutdown instructions are als
heater control box.
heater control box.
heater control box.
heater control box.
Form 43343530
Aug 2012
DANGER
o shown on the permanent nameplate label attached to the
o shown on the permanent nameplate label attached to the
o shown on the permanent nameplate label attached to the
-41-
to the "ON" position.
to the "OFF" position and turn