User Interfaces
18
Setup Check & Setup Modes (
This section is provided to aid the operator in making selections during the Setup Mode. It is
recommended that the operator fill in the selections in the proper blanks and then use this page
as a reference while programming the TA402A. The blocks shown below indicate the order of
options in the Setup Mode. To the right of each block is a description of the choice(s) that are
available. More information about making each selection is provided in the pages that follow.
Pass word
In hibit
Mode
A2 Alarm
Op tions
A1 Alarm
Op tions
Fault/In hibit
Op tion
Card Test
Op tions
Pass word
Op tions
Setup Check
Mode
)
continued
En ter the Pass word, if the Pass word is en abled.
En ter the In hibit Mode, if de sired.
Set the En er gized (En) / De- Energized (dE) Op tion
Set the Latch ing (LA) / Non- Latching (nL) Op tion
Set the Time De lay (1, 2, 4, or 8 sec onds)
Set the En er gized (En) / De- Energized (dE) Op tion
Set the Latch ing (LA) / Non- Latching (nL) Op tion
Set the Fault Ac ti vate (Ac) or not (nA) dur ing In hibit Op tion
Dis play will in di cate "ct" for 5 sec onds
Set the Alarm out puts for Ac tive (Ac) or Not Ac tive (nA)
Set the Pass word to be Dis abled (Pd) or En abled (PE)
If the Pass word is En abled:
Set the pass word dig its . . . . . . . .
Af ter all of the op tions have been se lected, the TA402A will en ter the Setup Check
Mode.
General Monitors
EN TER SE LEC TION
Left
Right