Setup Check & Setup Modes (
n
The last A2 alarm option to appear on
the display will be the alarm time delay.
If the A1 alarm is activated continuously
for the amount of time specified by this
option the A2 alarm outputs will
activate. The display will indicate the
current A2 alarm time delay in seconds
(figure 18).
Press the Mode/Select
switch repeatedly, until the desired A2
alarm time delay (1, 2, 4 or 8 seconds)
appears on the display. 4 is the factory
default for this selection.
Fig ure 18
A1 ALARM OPTIONS
n
Next, the A1 LED on the front panel
will
be
flashing
Energized/De-energized
displayed (figure 19). The display will
indicate the current selection, (En or
dE). Press the Mode/Select switch until
the
desired
option
De-Energized is the factory default for
this selection.
)
con tin ued
while
the
option
is
is
displayed.
User Interfaces
Fig ure 19
n
The A1 LED on the front panel will be
flashing while the latching/non-latching
option is displayed (figure 20).
display
will
indicate
selection, (nL or LA).
Mode/Select switch until the desired
option is displayed. Non-Latching is the
factory default for this selection.
Fig ure 20
21
The
the
current
Press the