Figure 3 Wire Strip Length; Figure 4 Rear Terminal Designations - General Monitors TA402A Instruction Manual

Zero two series trip amplifier module for flame detection applications
Table of Contents

Advertisement

Installation
10
Rear Terminal Connections (
Fig ure 6
The terminal designation for the Unaccept
output is:
Label
Term De scrip tion
UA
18d
The terminal designations for the Discrete
Inhibit indication is:
La bel
Term De scrip tion
CAL/INH
32z
If the Backwards Compatible configuration
is ordered, the CAL/INH will not be present
(pin 32z will be for 0v, alternate COM).
The terminal designations for the Flame
Detector connections are:
La bel
Term De scrip tion
WHT
26d,z Sig nal IN (Ana log)
RED
28d,z VDC Out (+24Vdc)
BLK
30d,z DC Com mon
Only one Flame De tec tor may be con nected to a Model TA402A.
Figure 7 illustrates the inter-connections for
the Trip Amplifier & the Flame Detector.
)
continued
Open Col lec tor Out put
Open Col lec tor Out put
General Monitors
Fig ure 7