2.1 System Specifications

Application:
Flame Detection.
Detector Type:
General Monitors' FL3000 and FL3100
Flame Detectors.
Measuring Ranges (flame detectors):
UV Wavelength . 185 to 260nm
IR Wavelength... 4.3um (centerline)
Typical response times for TA402A
System:
with FL3000, FL3100
with FL3001, FL3101
with FL3002, FL3102
Test Features:
Card - Functionality & Alarm Ramp
LED - Integrity of LED' s & Display
Front Panel Indicators:
DISPLAY - 2 x 7 Segments
A2 - Time Delayed Alarm
A1 - Immediate Warning
READY - Normal Operation
SETUP - Display / Change Parameters
Modes of Operation:
Setup, Setup Check, Inhibit & Normal
Approvals:
The Model TA402A is CSA certified.
Warranty:
Two Years
Module.
System,
The engineering
2 to 5 sec
< 1 sec
2 to 5 sec

2.2 Mechanical Specifications

Weight: 11.2 oz.
Length: 9.9 inches
Height: 6.825 inches
Width:
1.0 inches

2.3 Electrical Specifications

Input Power Requirement:
20 to 35Vdc @ 375mA max. (24Vdc,
9W nominal with field device).
Electrical Classification:
General Monitor' s FL3000 and FL3100
Series Flame Detectors are rated for use
in Class I, Division 1, Groups B, C & D;
Class II, Groups E, F & G and Class III.
The Model TA402A is designed for use
in non-hazardous environments.
Relay Contact Rating:
4A @ 250Vac, 3A @ 30Vdc resistive
max. DPDT for A1 & A2, SPDT for
Fault.
Open Collector Rating:
100mA @ 35 Vdc for A1, A2, Fault,
UA, FUA, CAL-OC, LA1 & LA2.
Cable Parameters:
Recommended
three
maximum
cable
between module and the Field Device
with 24Vdc nominal at the detector:
AWG
Feet
14
4500
16
2250
18
1600
20
1100
22

Specifications

(318 grams)
(251 mm)
(173 mm)
(25 mm)
wire
shielded,
lengths
allowable
Me ters
1372
685
488
335
750