Figure 5 Relay Protection Circuit For Ac Loads - General Monitors TA402A Instruction Manual

Zero two series trip amplifier module for flame detection applications
Table of Contents

Advertisement

Model TA402A
Rear
Terminal
(
)
continued
The electrical rating for all open collector
outputs is 100mA @ 35 Vdc.
Figure 8 illustrates some typical open
collector external circuits.
Fig ure 8
NOTE: When any Open Collector Output
is connected to a device not powered by the
same supply powering the TA402A, it will be
necessary to remove (cut) Jumper W11 (see
figure 33 on page 35).
The terminal designation for the Card Test
Input is:
La bel
Term
CT
16d
The Card Test Input is provided so that the
user can access the Card Test feature
remotely.
One end of a normally open
SPST switch is connected to this termination
and the other end is connected to system
common. To activate the feature, simply
press and hold the switch for as long as the
test time is to be run (the minimum runtime
for this test is equal to the A2 time delay).
Figure 9 is a block diagram that shows the
switch connections for the Card Test feature.
Connections
De scrip tion
Switch Con nec tion
Fig ure 9
The terminal designations for the Analog
Output Signal are:
La bel
Term
AO+
20d
AO-
22d
If the Analog Signal is not used a
jumper must be placed between 20d &
22d.
Figure 10 is a diagram of the Analog Signal
connections.
Fig ure 10
Installation
De scrip tion
Ana log Sig nal (plus)
Ana log Sig nal (mi nus)
11