Distant Installation - Drolet ULTRA FLAME DIRECT VENT GAS STOVE Installation And Operating Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

DISTANT INSTALLATION

4)
It is possible to use up to 25 feet of pipe and a wall vent terminal or roof vent terminal ( no
E5700 ) However, the following restrictions must be applied. (see figure, next page)
- Maximum vertical lenght is 10 feet with the wall vent terminal.
- Maximum horizontal lenght is 10 feet
- Number of 45° or 90° elbows is three
• For installation proceed in the same manner as the basement installation.
• The venting distant kit ( No E-5705 ) contain:
- (15 feet)
- (1)
- (2)
- (15 feet)
- (6)
- (24 feet)
- (30)
- (1)
• The following pieces must be supplied by the installer.
- Galvanized or black pipe minimum 24 gauges
- Appropriate roof flashing
- Roof braces ( if required )
• The clearance between the pipe and the combustible wall must be 2" from the pipe additional
radiation shield can be ordered. Part number is E-5710.
5" LOCKING BAND
5" FLEXIBLE FLUE PIPE
4" FOR BASEMENT OR DISTANT
INSTALLATION
of 4" diameter, 2 plys flexible pipe
4" diameter union
locking bands
high temperature insulation
spring spacers
of aluminium tape
metal screws
radiation shield
SCREWS
8"RIGID AIR INLET PIPE
15