Performing The Refrigerant Gas Leak Test - Samsung AEX060EDEHA Installation Manual

Air to water heat pump outdoor unit
Hide thumbs Also See for AEX060EDEHA:
Table of Contents

Advertisement

Performing the refrigerant gas leak test

f Use a manifold gauge for R-410A to prevent the inflow of foreign substances and resist against the internal
pressure.
f Pressure test with dry oxygen free nitrogen only.
Apply pressure to the liquid side pipe and gas
side pipe with Nitrogen gas of 4.1 MPa (41.8
kgf/cm²)
Keep it for minimum 24 hours to check if the
pressure drops.
If the pressure drops, check if there is gas leak.
Maintain 1.0MPa of the pressure before
performing vacuum drying and check further
gas leak.
Manifold gauge
Low pressure side
Service port
* Make sure to use a recommended bubble test solution for Gas Leak Test. Soap water could cause cracking of the
flare nuts or lead to corrosion of flared joints.
• You may get injured when the joint on the high pressure side detaches and the gas comes in contact with
your body. Make sure to tighten the joint to prevent such accidents.
CAUTION
If you apply pressure more than 4.1MPa, the pipes may be
damaged. Apply pressure using pressure regulator.
After applying Nitrogen gas, check the change of pressure
using pressure regulator.
If the pressure is changed, apply soapy water to check the
leak. Check the pressure of the Nitrogen gas again.
After checking first gas leak, maintain 1.0MPa to check further
gas leak.
High pressure side
Pressure adjustment
valve (mandatory)
Nitrogen
gas
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents