Samsung VRF DVM S2 Technical Data Book

R410a, 50hz, essential

Advertisement

VRF
Technical
Data Book
DVM S2 for Europe
(R410A, 50Hz, Essential)
Model : Essential Type

Advertisement

Table of Contents
loading

Summary of Contents for Samsung VRF DVM S2

  • Page 1 Technical Data Book DVM S2 for Europe (R410A, 50Hz, Essential) Model : Essential Type...
  • Page 2 History Version Modification Date Remark Release DVM S2 (R410A, 50Hz, Essential) for Europe TDB Ver.1.0 20.12.02 Updated all contents (Final Specification) Ver.2.0 21.02.05 Updated the Non-ducted spec in Specification page Ver.3.0 21.07.05...
  • Page 3 Nomenclature Outdoor Unit Model Name Buyer (1) Classification (5) Feature 1 Inverter (6) Feature 2 (2) Capacity Standard + General Temp.+ Module x 1/10 HP (3 digits) High EER + Low Temp. + Module High EER + General Temp. + Module Standard + General Temp.
  • Page 4 Features & Benefits Rebuilt on all new innovations Rethink your approach to air conditioning with the Samsung DVM S2. It delivers outstanding comfort and energy efficiency, even in extreme climates. Its intelligent features make installation and maintenance easier and more cost-effective.
  • Page 5 Triple Profile Scroll and efficient Optimal Discharge Superheat (DSH) Control technology. * Samsung circulates 14,400cc/sec refrigerant (= 90cc (displacement volume) x 160rps (revolutions per second)), while Company A circulates 12,480cc/sec (= 96cc x 130rps), Company B circulates 14,080cc/sec (= 88cc x 160rps) and Company C circulates 12,320cc/sec (= 88cc x 140rps).
  • Page 6: Table Of Contents

    Contents 1. Combination Table / Design Procedure & Combination Ratio 2. Specification 3. Electric Characteristics 4. Dimensional Drawing 5. Center of Gravity 6. Electrical Wiring Diagrams 7. Sound Data 8. Operation Range 9. Piping Diagram 10. Installation...
  • Page 7 1. Combination Table Essential System Model Capacity (HP) Number of Capa Model Name individual outdoor units 10HP AM100AXVDGH/EU 12HP AM120AXVDGH/EU 14HP AM140AXVDGH/EU 16HP AM160AXVDGH/EU 18HP AM180AXVDGH/EU 20HP AM200AXVDGH1EU 22HP AM220AXVDGH1EU 24HP AM240AXVDGH1EU 26HP AM260AXVDGH1EU 28HP AM280AXVDGH1EU 30HP AM300AXVDGH1EU 32HP AM320AXVDGH1EU 34HP AM340AXVDGH1EU 36HP...
  • Page 8 1. Combination Table External Appearance Essential Capa Capa Model Name Model Model Name Model [HP] [HP] AM260AXVDGH1EU AM100AXVDGH/EU AM280AXVDGH1EU AM120AXVDGH/EU AM300AXVDGH1EU AM140AXVDGH/EU AM320AXVDGH1EU AM160AXVDGH/EU AM340AXVDGH1EU AM180AXVDGH/EU AM360AXVDGH1EU AM200AXVDGH1EU AM380AXVDGH1EU AM220AXVDGH1EU AM400AXVDGH1EU AM240AXVDGH1EU...
  • Page 9: Combination Table / Design Procedure & Combination Ratio

    1. Design Procedure & Combination Ratio Combination Ratio (Connection Ratio) Definition of Combination Ratio, CR Sum of Nominal Cooling Capacity of Indoor units CR = * 100% Nominal Cooling Capacity of Outdoor unit Constraints of Allowable Combination Ratio DVM S systems are normally designed to utilize a CR 50% to 130% to ensure effective load balancing between indoor units and outdoor unit.
  • Page 10 Satisfying cooling & heating comfort The Maximum Capacity of outdoor unit at design condition calculated from Samsung capacity data table or design tool (DVM Pro) should always be the same or greater than System Peak Load (Block Load) defined in table 1.
  • Page 11 1. Design Procedure & Combination Ratio Combination Ratio (Connection Ratio) Allowable CR limit to avoid abnormal sound level risks in heating operation f If the CR exceeds 130%, in a specific case of heating operation, an indoor unit may have higher sound level than the level specified in the technical documents.
  • Page 12 NOTE Fig. 2. Please contact your local Samsung representative for further details if the project requires you to design the project with a connection ratio greater than 130%.
  • Page 13: Specification

    2. Specification Essential Model Name AM100AXVDGH/EU AM120AXVDGH/EU AM140AXVDGH/EU Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Outdoor unit module 4 Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode HEAT PUMP HEAT PUMP...
  • Page 14 When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information. 9) In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
  • Page 15 2. Specification Essential Model Name AM160AXVDGH/EU AM180AXVDGH/EU AM200AXVDGH1EU AM100AXVDGH/EU Outdoor unit module 1 AM100AXVDGH/EU Outdoor unit module 2 Outdoor unit module 3 Outdoor unit module 4 Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode HEAT PUMP...
  • Page 16 When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information. 9) In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
  • Page 17 2. Specification Essential Model Name AM220AXVDGH1EU AM240AXVDGH1EU AM260AXVDGH1EU AM100AXVDGH/EU AM100AXVDGH/EU AM100AXVDGH/EU Outdoor unit module 1 AM120AXVDGH/EU AM140AXVDGH/EU AM160AXVDGH/EU Outdoor unit module 2 Outdoor unit module 3 Outdoor unit module 4 Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode...
  • Page 18 When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information. 9) In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
  • Page 19 2. Specification Essential Model Name AM280AXVDGH1EU AM300AXVDGH1EU AM320AXVDGH1EU AM120AXVDGH/EU AM120AXVDGH/EU AM160AXVDGH/EU Outdoor unit module 1 AM160AXVDGH/EU AM180AXVDGH/EU AM160AXVDGH/EU Outdoor unit module 2 Outdoor unit module 3 Outdoor unit module 4 Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode...
  • Page 20 When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information. 9) In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
  • Page 21 2. Specification Essential Model Name AM340AXVDGH1EU AM360AXVDGH1EU AM380AXVDGH1EU AM160AXVDGH/EU AM180AXVDGH/EU AM100AXVDGH/EU Outdoor unit module 1 AM180AXVDGH/EU AM180AXVDGH/EU AM120AXVDGH/EU Outdoor unit module 2 AM160AXVDGH/EU Outdoor unit module 3 Outdoor unit module 4 Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode...
  • Page 22 When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information. 9) In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
  • Page 23 2. Specification Essential Model Name AM400AXVDGH1EU AM100AXVDGH/EU Outdoor unit module 1 AM120AXVDGH/EU Outdoor unit module 2 AM180AXVDGH/EU Outdoor unit module 3 Outdoor unit module 4 Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 Mode HEAT PUMP Performance Cooling(Rated) 112.0 Capacity Heating(Rated)
  • Page 24 When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information. 9) In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
  • Page 25: Electric Characteristics

    3. Electric Characteristics Essential Capacity Power Supply Voltage Range Running Current [A] Current [A] ODU Fan Motor Model Name Min. Max. Voltage Cooling Heating FLA [A] (-10%) (+10%) 28.0 AM100AXVDGH/EU 380-415 20.50 14.34 23.0 0.63 33.6 AM120AXVDGH/EU 380-415 22.01 16.45 25.0 0.63 40.0...
  • Page 26: Dimensional Drawing

    4. Dimensional Drawing Outdoor unit • AM100AXVDGH/EU Unit: mm (inches) Section A NOTE 1 Detail A and SECTION B-B indicate the dimension after fixing the attached piping. 2 Item 3-6: Knock-out hole 3 View C indicate the dimension of knock-out hole (bottom) 4 Pipe [Ø, mm(inch)]: Brazing connection Liquid pipe...
  • Page 27 4. Dimensional Drawing Outdoor unit • AM120AXVDGH/EU, AM140AXVDGH/EU Unit: mm (inches) Section A NOTE 1 Detail A and SECTION B-B indicate the dimension after fixing the attached piping. 2 Item 3-6: Knock-out hole 3 View C indicate the dimension of knock-out hole (bottom) 4 Pipe [Ø, mm(inch)]: Brazing connection Liquid pipe...
  • Page 28 4. Dimensional Drawing Outdoor unit • AM160AXVDGH/EU, AM180AXVDGH/EU Unit: mm (inches) NOTE 1 Detail A and SECTION B-B indicate the dimension after fixing the attached piping. 2 Item 3-6: Knock-out hole 3 View C indicate the dimension of knock-out hole (bottom) 4 Pipe [Ø, mm(inch)]: Brazing connection Liquid pipe Gas pipe...
  • Page 29: Center Of Gravity

    5. Center of Gravity Outdoor unit Unit: mm (inches) Model 458[18 - 1/16] 694[27 - 5/16] AM100AXVDGH/EU 340[13 - 3/8]...
  • Page 30 5. Center of Gravity Outdoor unit Unit: mm (inches) Model AM120AXVDGH/EU 351 [13 - 13/16] 461 [18 - 1/8] 694 [27 - 5/16] AM140AXVDGH/EU...
  • Page 31 5. Center of Gravity Outdoor unit Unit: mm (inches) Foundation bolt hole Model AM160AXVDGH/EU 502[19 - 3/4] 719[28 - 5/16] 345[13 - 9/16] AM180AXVDGH/EU...
  • Page 32: Electrical Wiring Diagrams

    6. Electrical Wiring Diagrams Outdoor unit AM100~120AXVDGH/EU INV PCB Printed circuit board (inverter) EVI-OUT(10K) Thermistor (EVI-out_10kohm) EMI PCB Printed circuit board (emi) EVI-IN(10K) Thermistor (EVI-in_10kohm) MAIN PCB Printed circuit board (main) SUCT1(10K) Thermistor (Suction Temp.1_10Kohm) COMPRESSOR Motor (compressor) SUCT2(10K) Thermistor (Suction Temp.2_10Kohm) FAN1 Motor (fan1) SNOW SENSOR...
  • Page 33 6. Electrical Wiring Diagrams Outdoor unit AM140~180AXVDGH/EU INV PCB Printed circuit board (inverter) EVI-OUT(10K) Thermistor (EVI-out_10kohm) EMI PCB Printed circuit board (emi) EVI-IN(10K) Thermistor (EVI-in_10kohm) MAIN PCB Printed circuit board (main) SUCT1(10K) Thermistor (Suction Temp.1_10Kohm) COMPRESSOR Motor (compressor) SUCT2(10K) Thermistor (Suction Temp.2_10Kohm) FAN1 Motor (fan1) SNOW SENSOR...
  • Page 34: Sound Data

    7. Sound Data Summary Sound Power Capacity Sound Pressure dB(A) Model Name dB(A) Cooling Heating 28.0 AM100AXVDGH/EU 33.6 AM120AXVDGH/EU 40.0 AM140AXVDGH/EU 45.0 AM160AXVDGH/EU 50.4 AM180AXVDGH/EU 56.0 AM200AXVDGH1EU 61.6 AM220AXVDGH1EU 68.0 AM240AXVDGH1EU 73.0 AM260AXVDGH1EU 78.6 AM280AXVDGH1EU 84.0 AM300AXVDGH1EU 90.0 AM320AXVDGH1EU 95.4 AM340AXVDGH1EU 100.8 AM360AXVDGH1EU...
  • Page 35 7. Sound Data Sound Pressure level Unit: dB(A) Model Cooling Silent 1 Silent 2 Silent 3 Microphone AM100AXVDGH/EU AM120AXVDGH/EU 1.5m Front AM140AXVDGH/EU AM160AXVDGH/EU • NR Curve 1) AM100AXVDGH/EU 2) AM120AXVDGH/EU 3) AM140AXVDGH/EU 4) AM160AXVDGH/EU NOTE • Specifications may be subject to change without prior notice. - Sound pressure level is obtained in an anechoic room.
  • Page 36 7. Sound Data Sound Pressure level Unit: dB(A) Model Cooling Silent 1 Silent 2 Silent 3 Microphone AM180AXVDGH/EU 1.5m Front • NR Curve 1) AM180AXVDGH/EU NOTE • Specifications may be subject to change without prior notice. - Sound pressure level is obtained in an anechoic room. - Sound pressure level is a relative value, depending on the distance and acoustic environment.
  • Page 37 7. Sound Data Sound Power level Unit: dB(A) Model Power AM100AXVDGH/EU AM120AXVDGH/EU AM140AXVDGH/EU AM160AXVDGH/EU • NR Curve 1) AM100AXVDGH/EU 2) AM120AXVDGH/EU 3) AM140AXVDGH/EU 4) AM160AXVDGH/EU NOTE • Specifications may be subject to change without prior notice. - Sound power level is an absolute value that a sound source generates. - dBA = A-weighted sound power level.
  • Page 38 7. Sound Data Sound Power level Unit: dB(A) Model Power AM180AXVDGH/EU • NR Curve 1) AM180AXVDGH/EU NOTE • Specifications may be subject to change without prior notice. - Sound power level is an absolute value that a sound source generates. - dBA = A-weighted sound power level.
  • Page 39: Operation Range

    8. Operation Range Cooling Heating Continuous Warming Operation Range Continuous Operation Range Operation Range “Expand Operational Temperature Range” Option 25 27 Indoor(˚CWB) Indoor(˚CWB) (1) The operating range is shown in these figures (2) The assumed installation condtions are as follows - Outdoor units and indoor units combination - The Pipe length(including elbow) is 5m - The Level difference is 0m...
  • Page 40 8. Operation Range Defrosting correction factor The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the defrosting operation is in progress. The capacity values, which take these factors into account, in other words, the integrated heating capacity values, can be calculated as follows : Formula : A = B ×...
  • Page 41: Piping Diagram

    9. Piping Diagram Outdoor unit (1) AM100~140AXVDGH Ball Valve - Gas pipe Outdoor Fan 1 (OF1) (BV_G) Thermistor - Ambient (T_A) Motor for Outdoor Fan 1 (OFM1) Thermistor - Cond Out (T_CO) Heat Exchanger - Main (HX_M) Thermistor - Electronic Suction pipe Expansion Check Valve -...
  • Page 42 9. Piping Diagram Outdoor unit (2) AM160~180AXVDGH Ball Valve - Outdoor Fan 1 (OF1) Gas pipe Outdoor Fan 2 (OF2) (BV_G) Thermistor - Ambient (T_A) Motor for Outdoor Fan 1 (OFM1) Motor for Outdoor Fan 2 (OFM2) Thermistor - Cond Out (T_CO) Heat Exchanger - Main (HX_M) Thermistor -...
  • Page 43: Installation

    – Check the installation site every 3 months and perform anti- • Place where structure can bear the weight and vibration of the corrosion treatment such as R-Pro supplied by SAMSUNG outdoor unit. (Code : MOK-220SA) or commercial water repellent grease •...
  • Page 44 10. Installation Outdoor unit Module installation • When you install the outdoor unit in high places such as a roof, install fence or guardrail around it. When there is no fence or guardrail, service person could fall. • Do not install the product in places where corrosive gases such (Unit : mm) as sulfur oxides, ammonia, and sulfurous gas are produced.
  • Page 45 10. Installation Outdoor unit Pr Preparing mat eparing material erials and s and t t ool ools s • You must keep the installation manual until the installation is Classification Model Name Specification finished. MXJ-YA1500M 22.4 kW and below • Hand over the installation manual to the customer after finishing the installation.
  • Page 46 10. Installation Outdoor unit Base ground construction (Unit : mm) DVM S2 Small Type DVM S2 Large Type Classification (mm) W930 x H1695 x D765 W1295 x H1695 x D765 (Unit : mm) Bottom surface of the base ground 1295 must be horizontally leveled 1155 Draining pit...
  • Page 47 10. Installation Outdoor unit • Caution for installing discharge duct CAUTION – Static pressure of the discharge duct should be within the • Cautions regarding on connecting the anchor bolt standard specification when installing the duct. – Tighten the rubber washer to prevent the bolt connection –...
  • Page 48 10. Installation Outdoor unit WARNING • Should adopt bar type louver. Don’t use a type of rain resistance louver. [Bar type louver] [Rain resistance louver] Installing the outdoor unit in windy region • In windy regions such as near sea shores, protection wall or •...
  • Page 49 10. Installation Outdoor unit WARNING Installation process/ Compatibility with Tool purpose conventional tool • When installing, make sure there is no leakage. When Compatible (Use products collecting the refrigerant, stop the compressor first before which contain the check removing the connection pipe. If the refrigerant pipe is not valve to prevent the oil properly connected and the compressor works with the service Vacuum...
  • Page 50 10. Installation Outdoor unit 33.6 kW 40.0 kW 61.6 kW Ex.) 135.2 kW Pipe size (mm) Capacity (kW) Liquid 33.6 Ø 12.70 Ø 28.58 73.6 Ø 19.05 Ø 34.92 135.2 Ø 19.05 Ø 41.28 Size of the pipe connected to the outdoor unit (A) Size of the pipe between the branch joint and the indoor unit Select the size of the main pipe according to the below table.
  • Page 51 10. Installation Outdoor unit When all the following conditions are met, install the main liquid pipe that is one step smaller to reduce piping load and the amount of refrigerant. Note that the refrigerant for the main liquid pipe must be added by the specified amount upon reduction. Condition 1: In case the length for vertical piping is less than 40 m Condition 2: Max.
  • Page 52 10. Installation Outdoor unit Additional refrigerant 46.4 kW Ø12.70 (5 m) 4.5 kW Ø12.70 (5 m) Ø6.35 (5 m) 5.6 kW Ø12.70 (5 m) Ø6.35 (10 m) Ø9.52 (10 m) 5.6 kW Ø6.35 (15 m) Ø9.52 (10 m) Ø6.35 (5 m) Ø9.52 (10 m) Ø9.52 (10 m) Ø9.52 (10 m)
  • Page 53 10. Installation Outdoor unit • Amount of additional refrigerant for each indoor unit ( ) (Unit: kg) Refrigerant Amount (kg /Unit) Model 1.5 1.7 2.2 2.8 3.2 3.6 4.0 4.5 5.6 6.0 7.1 8.2 9.0 9.3 11.0 11.2 12.8 14.0 16.0 18.0 22.0 22.4 25.0 28.0 32.0 50.0 500CMH 1000CMH Interior 1way cassette (JSF-0) (AM***HN1DEH/**) 0.15 0.15...
  • Page 54 10. Installation Outdoor unit • If AHU kit is included among the indoor units, you must add 0.063kg of refrigerant for every 1kW of the AHU capacity increase. Note1) In case the capacity conjunction of the Hydro Unit HT exceeds 50 % among the total indoor unit, please don’t put the additional refrigerant.
  • Page 55 10. Installation Outdoor unit Pipe installation for an outdoor unit CAUTION 1 Direction of the pipe • Caution for using knock-out hole Refrigerant pipe can be withdrawn from the front, left and right side. Take necessary method to install the pipes according to the condition of the installation site.
  • Page 56 10. Installation Outdoor unit Service valve Service valve Service port Service port Temperature Temperature sensor sensor Wet towel Wet towel < H/P > < H/R > 1 Pipe installation between the outdoor units • You will need branch joints, which is an optional accessory, for connecting in between outdoor units in order to combine outdoor units in module.
  • Page 57 10. Installation Outdoor unit Examples of refrigerant pipe installation 1 Using Y-joint 2 Using distribution header Allowable length of the refrigerant pipe and the installation examples Classification Single Installation Module installation Outdoor unit Outdoor unit Branch joint Branch joint Installing only with Y-joint Indoor unit Indoor unit Outdoor unit...
  • Page 58 10. Installation Outdoor unit Classification Example Remarks Installing only with a+b+c+d+e+f+g+p ≤ Y-joint 200m(220m) Equivalent length Actual length 200m and a+b+h ≤ 200m (220m), Installing with Y-joint Y-joint: 0.5 m, (Equivalent below (220m and distribution header Distribution header: a+i+k ≤ 200m (220m) length) and below) Installing only with...
  • Page 59 10. Installation Outdoor unit Classification Condition Example First branch joint ~ 45m ≤ b+c+d+e+f+g+p ≤ 90m: branch pipes (b, c, d, e, f, g) size must Farthest Indoor unit be increased by 1 grade If the size of pipe (main pipe), between the first branch joint and the outdoor unit, is not increased by 1 grade, a+(b+c+d+e+f+g)×2 +h+i+j+k+l+m+n+p ≤...
  • Page 60 10. Installation Outdoor unit • When installing outdoor units in module, select the power NOTE supply cable according to the sum of outdoor unit capacity. • This device is intended for the connection to a power supply (Refer to the table for each model) system with a maximum permissible system impedance shown •...
  • Page 61 10. Installation Outdoor unit Main unit Sub unit Sub unit ELCB ELCB ELCB MCCB+ MCCB+ MCCB+ Protection tube Ground cable Ground cable Ground cable Communication cable Communication Communication Power • ground cable between cable between cable Power cable outdoor units Power cable outdoor units Power cable...
  • Page 62 10. Installation Outdoor unit Power wiring diagram Supplying 3 phase 4 wires (380-415 V~) <When the module combination is in the tables of "Outdoor unit combination"> 3 phase 4 wires Main unit Sub unit 1 Sub unit 2 (380-415 V~) Main unit Sub unit MCCB+ ELCB Single phase 2 wires...
  • Page 63 10. Installation Outdoor unit Selecting solderless ring terminal • Select a solderless ring terminal for a power cable according to the nominal dimensions for cable. • Apply insulation coating to the connection part of the solderless ring terminal and the power cable. Silver solder Nominal dimensions for cable (mm Nominal dimensions for screw (mm)
  • Page 64 10. Installation Outdoor unit 1 Closing the cover Fixing the power cable 3 phase 4 wires (380-415 V~) ELCB Sub unit MCCB+ communication cable Sub unit Screw Tightening torque for terminal (N∙m) communication cable 1.2~1.8 Single phase (220-240 V) power cable Sub unit 3 5.5~7.3 3 phase (380-415 V) power cable phase 380-...
  • Page 65 10. Installation Outdoor unit Installing the Solution device Connect the ring terminal of 3 phase cable 1 Cut the power cable to an appropriate length and connect it • When the number of indoor units installed with the outdoor with the solderless terminal. unit is 16 or less 2 After connecting the power cable to the terminal as seen in the illustration, fix it with cable tie.
  • Page 66 2021.07 Ver.3.0 Samsung Electronics Co., LTD. Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677 Website : www.samsung.com, https://partnerhub.samsung.com Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice.