Making A Continuity Measurement; Storing / Downloading Results (Mft1730 Only); Continuity Buzzer On/Off; Switch Probe (Sp5) - Megger MFT1700 series User Manual

Mft1700 series multifunction testers
Hide thumbs Also See for MFT1700 series:
Table of Contents

Advertisement

5.2

Making a CONTINUITY measurement

.1
Set the Primary (Left) range knob to
the
position).
 
.2
Connect two test leads to the L1 (+ve) and L2 (-ve) terminals on the instrument.
A continuity measurement is made automatically.
NOTES: Measurements are prevented when:
A resistance of > 99,9 kΩ is present
Circuit voltages in excess of 4 V are detected.
5.3

Storing / downloading results (MFT1730 only)

For full details see Appedix A and B.
Once the display shows a value it will automatically be logged into temporary memory. Unless stored, this will be over
written by the next measurement.
To store this result or to send it to a PowerSuite compatible device, refer to Appedix A and B.
5.4

Continuity Buzzer ON/OFF

Whilst in the continuity range, press the MODE button
 
5.5

Switch probe (SP5)

In the CONTUNUITY/RESISTANCE mode all measurements can be made with the remote switch probe (SP5). Tests are
automatic and do not require the TEST button to be pressed.
.1
Connect the switch probe to the switch probe socket L1 (+ve). The switch probe replaces the standard RED test
lead. Test as in 5.2 above.
 
range. (The position of the right hand rotary range knob must not be in
 
. This will toggle the buzzer ON and OFF.
 
Buzzer ON =
Buzzer OFF = No symbol