These must be read and understood before the instrument is used. They must be observed during use.
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS.
Users of this equipment and/or their employers are reminded that National Health and Safety Legislation requires them to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical danger and risk of electrical injury such as inadvertent short circuits. Where the assessments show that the risk is significant then the use of fused test leads may be appropriate.
Symbols used on the instrument:
BS EN 61010 defines measurement categories from I to IV relating transient over voltages and the location within the electrical installation. This instrument is designed for use at Category III (Building installation/distribution board level) up to 600 V (maximum) rms to earth and 600 V (maximum) rms between terminals. It may also be used at Category IV (Primary supply level) on 300 V rms phase to earth systems.
All circuits must be isolated before an insulation or continuity test.
The instrument will automatically display voltage between 25 V and 600 Vac or dc when connected to the circuit under test.
Remove the source of any voltage before continuing to test.
To remove test lead resistance before continuity tests:
Lead null value is automatically stored until reset.
To remove, press the TEST button again with leads open circuit.
NOTE:
If ">100.0 Ω " is displayed the resistance of the circuit is over-range.
[]
If a circuit voltage >50 V is detected, further testing will be prevented.
After testing ensure the display returns to Zero (circuit is discharged) before removing test leads.
Error messages:
>100.0 Ω Continuity over-range
<0.01 M Ω Insulation test result is under-range
>1000 M Ω Insulation test result is over-range
UNC Uncalibrated
E17 Instrument not configured to a specific type.
Low battery voltage is indicated by the symbol in the display. To maintain performance the batteries should be replaced at this point.
Uses 6 x 1.5 V AA (LR6) alkaline dry cells or NiMH rechargeable batteries.
To replace batteries switch off instrument and disconnect test leads from the circuit under test.
Remove the rear battery cover and replace the batteries. Do not mix old and new batteries.
OBSERVE CORRECT POLARITY. Incorrect battery polarity could cause batteries to leak and damage the instrument.
A blown fuse is indicated by the symbol f in the display.
To replace the fuse remove battery cover and replace fuse with type: 500 mA (F) HBC 50 kA 600 V.
Cleaning:
Wipe disconnected instrument with a clean cloth dampened with soapy water or Isopropyl Alcohol (IPA).
Insulation ranges | |
Test voltage accuracy: | -0% +25% over full operating temperature |
Nominal Test Voltage: | 1000 V, 500 V, 250 V (d.c.) |
Measuring Range: | 10 kΩ - 999 MΩ on all ranges |
Short Circuit Current: | 2 mA -1 mA +0 mA |
Test Current on Load: | 1 mA at min. pass values of insulation (as specified in BS 7671, EN61557, HD 384 and IEC 364) |
Accuracy (at 20°C) | ±3%, ±2 digits (or 30% of reading 200 kΩ to 10 MΩ) |
Continuity ranges | |
Measuring Range: | 0,01 Ω - 100 Ω (0 -50 Ω on analogue scale) |
Open Circuit Voltage: | 5 V ± 1 V |
Short Circuit Current: | 205 mA, ± 5 mA (0 to 10 Ω) (>20 mA up to 100 Ω) |
Accuracy (at 20°C): | ±3% ±2 digits |
Null Offset Adjust: | 0 – 9 Ω |
Continuity Buzzer: | Operates at < 5 Ω Response time <20 ms |
Default voltmeter: | all test modes except off |
Test inhibit: | >50 V |
AutoPower Down: | Operates after 10 minutes if left in standby mode. |
Environmental | |
Operating Range: | -10°C to +55°C |
Operating Humidity: | 93% R.H. at +40°C max. |
Storage Range: | -25°C to +65°C |
Dimensions: | 195 mm x 98 mm x 40 mm |
Weight: | 550 gms |
Battery: | 6 x 1,5 V cells IEC LR6 type (AA alkaine) or NiMH rechargeable |
Battery life: | 3000 consecutive tests (5 sec/test) on any test using 2Ah batteries |
Fuses | |
Terminals: | 500 mA (F) 600 V, 32 x 6 ceramic HBC 50 kA minimum |
Meets the requirements of BS EN61010-1, Cat III 600 V phase to earth. Refer to safety warnings supplied.
After an insulation test, the circuit under test will be discharged automatically. Any voltage present will be indicated on the display so that the discharge can be monitored.
EMC
In accordance with IEC 61326 including amendment No.1
The instrument contains static sensitive devices, and care must be taken in handling the printed circuit board. If an instrument's protection has been impaired it should not be used, but sent for repair by suitably trained and qualified personnel. The protection is likely to be impaired if for example, it shows visible damage, fails to perform the intended measurements, has been subjected to prolonged storage under unfavourable conditions, or has been subjected to severe transport stresses.
NEW INSTRUMENTS ARE GUARANTEED FOR 3 YEARS FROM THE DATE OF PURCHASE BY THE USER.
Note:
Any unauthorized prior repair or adjustment will automatically invalidate the Warranty.
For service requirements for Megger Instruments contact:
Megger Limited | Megger |
Archcliffe Road | Valley Forge Corporate Centre |
Dover | 2621 Van Buren Avenue |
Kent CT17 9EN | Norristown PA 19403 |
England. | U.S.A. |
Tel: +44 (0) 1304 502 243 | Tel: +1 610 676 8579 |
Fax: +44 (0) 1304 207 342 | Fax: +1 610 676 8625 |
Megger operate fully traceable calibration and repair facilities, ensuring your instrument continues to provide the high standard of performance and workmanship you expect. These facilities are complemented by a worldwide network of approved repair and calibration companies to offer excellent inservice care for your Megger products.
A list of Approved Service Centres may be obtained from the UK address above, or from Megger's website at www.megger.com
Megger Limited
Archcliffe Road, Dover
Kent CT17 9EN England
T +44 (0)1 304 502101
F +44 (0)1 304 207342
E uksales@megger.com
Megger
4271 Bronze Way, Dallas,
Texas 75237-1019 USA
T +1 800 723 2861 (USA ONLY)
T +1 214 333 3201
F +1 214 331 7399
E ussales@megger.com
Megger
Z.A. Du Buisson de la Couldre
23 rue Eugène Henaff
78190 TRAPPES France
T +33 (0)1 30.16.08.90
F +33 (0)1 34.61.23.77
E infos@megger.com
Megger Pty Limited
Unit 26 9 Hudson Avenue
Castle Hill
Sydney NSW 2125 Australia
T +61 (0)2 9659 2005
F +61 (0)2 9659 2201
E ausales@megger.com
Megger Limited
110 Milner Avenue Unit 1
Scarborough Ontario M1S 3R2
Canada
T +1 416 298 9688 (Canada only)
T +1 416 298 6770
This instrument is manufactured in the United Kingdom.
The company reserves the right to change the specification or design without prior notice.
Megger is a registered trademark
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Megger MIT200 Series - Insulation And Continuity Tester Manual