Megger MFT1700 series User Manual page 17

Mft1700 series multifunction testers
Hide thumbs Also See for MFT1700 series:
Table of Contents

Advertisement

.3
Connect test leads as below, with the Red test lead connected to the L1 (Red terminal on the MFT and the Green
test lead connected to the Green (L2) terminal.
 
The Blue (L3) test lead can be connected to enable "reverse polarity" warnings
.4
Press the Function key <-> to select the "2Hi" mode.
.5
Press 'TEST' to start the test sequence. This can be automated in SETUP so the test starts when contacting the
circuit. See section 10 Setup.
.6
On completion of the test, the display will show the loop resistance on the large display segments, and the fault
current on the small display segments.
7.2.3
Earth Loop measurements with an RCD in circuit
Loop testing L-N through and RCD will not trip it, using the 2Hi test mode. However testing Phase to Earth requires a test that draws
less current and help prevent the RCD tripping. It is impossible to guarantee that an RCD will not trip. If there is a risk associated with
tripping an RCD alternative methods should be used for testing the circuit.
Using 3 wire measurement - 3Lo
.1
Set the LEFT rotary range knob to the
.2
On the MFT1720 and MFT1730 set the RIGHT rotary knob to
 
 
 
range.
.
 
17