CAUTION
Sharp edges can cause personal injury. Avoid contact with them.
Use care and wear protective clothing, safety glasses and gloves
when handling parts and servicing heat pumps.
Upon receipt of the equipment, check carton for visible
damage. Make a notation on the shipper's delivery
ticket before signing. If there is any evidence of rough
handling, immediately open the cartons to check for
concealed damage. If any damage is found, notify
the carrier within 48 hours to establish your claim and
request their inspection and a report. The Warranty
Claims Department should then be contacted.
Do not stand or transport the machines on end. For
storing, each carton is marked with "up" arrows.
In the event that elevator transfer makes up-ended
positioning unavoidable, do not operate the machine
until it has been in the normal upright position for at least
24 hours.
Temporary storage at the job site must be indoor,
completely sheltered from rain, snow, etc. High or low
temperatures naturally associated with weather patterns
will not harm the units. Excessively high temperatures,
140°F (60°C) and higher, may deteriorate certain plastic
materials and cause permanent damage.
IMPORTANT
This product was carefully packed and thoroughly inspected
before leaving the factory. Responsibility for its safe delivery
was assumed by the carrier upon acceptance of the
shipment. Claims for loss or damage sustained in transit
must therefore be made upon the carrier as follows:
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted
on the freight bill or carrier's receipt, and signed by the
carrier's agent. Failure to adequately describe such external
evidence of loss or damage may result in the carrier's
refusal to honor a damage claim. The form required to file
such a claim will be supplied by the carrier.
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which
does not become apparent until the product has been
unpacked. The contents may be damaged in transit due
to rough handling even though the carton may not show
external damages. When the damage is discovered upon
unpacking, make a written request for inspection by the
carrier's agent within fifteen (15) days of the delivery date
and file a claim with the carrier.
www.DaikinApplied.com

Pre-Installation

The installer must determine and follow all applicable codes
and regulations. This equipment presents hazards of electricity,
rotating parts, sharp edges, heat and weight. Failure to read and
follow these instructions can result in property damage, severe
personal injury or death. This equipment must be installed by
experienced, trained personnel only.
1 .
To prevent damage, do not operate this equipment
for supplementary heating and cooling during the
construction period.
2 .
Inspect the carton for any specific tagging numbers
indicated by the factory per a request from the
installing contractor. At this time the voltage, phase
and capacity should be checked against the plans.
3 .
Check the unit size against the plans to verify that
the unit is being installed in the correct location.
4 .
Before installation, check the available closet
dimensions versus the dimensions of the unit.
5 .
Note the location and routing of water piping,
condensate drain piping, and electrical wiring. The
locations of these items are clearly marked on
submittal drawings.
6 .
The installing contractor will find it beneficial to
confer with piping, sheet metal, and electrical
foremen before installing any unit.
Note: Check the unit data plate for correct voltage with
the plans before installing the equipment. Also,
make sure all electrical ground connections are
made in accordance with local code.
7 .
The contractor shall cover the units to protect the
machines during finishing of the building. This is
critical while spraying fireproofing material on bar
joists, sandblasting, spray painting and plastering.
8 .
The overall opening of the doorway to mechanical
room must be 2" wider than the unit for easy
installation and/or removal.
Table 1: Overall Unit Dimensions
Unit Size
009 – 012
015 – 024
030 – 036
042 – 048
060 – 070
Note: Dimensions are approximate.
5
Enfinity Vertical Water Source Heat Pumps • IM 930-6
r
s
eCeiving and
WARNING
Dimensions
22¼"D x 20"W x 37"H
24¼"D x 23"W x 46½"H
24¼"D x 23"W x 50½"H
32½"D x 25"W x 46½"H
32½"D x 25"W x 58½"H
torage