Table 22: Occupied, Bypass Mode, Standby or Tenant Override Modes
Description*
Occupied, Bypass Mode, Standby or
Tenant Override Modes
• Unit is operating normal. It may currently have a control signal or ready to operate when a control signal is active.
Troubleshooting Refrigeration Circuit
Figure 33: Troubleshooting Refrigeration Circuit
Symptom
Head Pressure
Charge
Undercharge System
(Possible Leak)
Overcharge System
Low Air Flow Heating
Low Air Flow Cooling
Low Water Flow Heating
Normal
Low Water Flow Cooling
High Air Flow Heating
High Air Flow Cooling
High Water Flow Heating
Normal
High Water Flow Cooling
TXV Restricted
www .DaikinApplied .com
Type
Mode
Suction
Compressor
Pressure
Amp Draw
Low
Low
Low
High
High
High
High
High
High
Low
Low
Low
Low
Low
Low
Normal
High
High
High
Low
Low
Low
Low
High
Normal
Low
Normal
Low
Low
Low
Normal
High
Low
Low
Yellow
OFF
Super Heat
Subcooling
High
Low
Normal
High
High
Low
Normal
Low
High
Normal
Low
High
High
Low
Low
High
High
Low
High
Normal
Low
High
High
High
35
Enfinity Vertical Water Source Heat Pumps • IM 930-6
t
roubleshooting
Green
Red
ON
OFF
Water
Air Temp
(loops)
Safety Lock Out
Differential
Temp
Differential
Low
Low
Low Pressure
Normal
Normal
High Pressure
Low
High
Low
High Pressure
High
Low
Low
High
Low
High
High Pressure
Low
Low
Low
Normal
High Pressure
Normal
Low
High Pressure
Normal
Low
Low
Low
Low Temp
Low Temp
Low Temp
Low Temp