SPLIT SYSTEM HEATING PERFORMANCE
MODEL: SSZ160601A* / CA*F4860*6A* + TXV / MBE2000**-1
65
60
55
MBh
71.6
67.8
63.8
Delta T
36.9
34.9
32.8
KW
4.73
4.63
4.53
AMPS
21.7
20.0
18.7
COP
4.44
4.29
4.12
EER
15.2
14.7
14.1
HI PR
395
379
364
LO PR
133
124
116
High pressure is measured at the suction service valve ( the larger valve).
Low pressure is measured at the gauge port connection.
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
*Note: Shaded area is ARI Rating Conditions at 47° outdoor ambient temberature
EXPANDED PERFORMANCE DATA
Outdoor Ambient Temperature
50
47
45
40
59.7
57.0
55.2
51.3
30.7
29.3
28.4
26.4
4.38
4.44
4.34
4.25
17.6
16.9
16.6
15.6
3.94
3.81
3.73
3.54
13.5
13.0
12.7
12.1
348
340
334
321
106
101
97
89
35
30
25
20
47.3
44.9
41.4
38.1
24.3
23.1
21.3
19.6
4.15
4.27
4.16
4.06
14.8
14.1
13.5
12.8
3.34
3.08
2.91
2.75
11.4
10.5
9.9
9.4
308
295
282
270
79
71
64
56
SSZ160601A*
HEATING OPERATION
17
15
10
5
36.0
34.7
31.1
27.6
18.5
17.8
16.0
14.2
4.00
3.96
3.86
3.76
12.5
12.3
11.6
10.8
2.63
2.56
2.36
2.15
9.0
8.7
8.1
7.3
264
259
249
240
52
50
43
37
AMPS = Outdoor unit amps (comp.+fan)
KW = Total system power
0
-5
-10
24.0
20.5
16.8
12.4
10.6
8.6
3.66
3.55
3.45
10.2
9.3
8.4
1.92
1.69
1.42
6.6
5.8
4.9
230
222
214
31
27
21
23