Function
Options:
Velocity V1 Fancoil
General Purpose
Option "Velocity V1 Fancoil": the output relay can be used to control the velocity
V1 of a fan coil in case a fan coil is used.
The type of fan coil can be selected with the parameter "Fancoil Type" in the
"Temperature Regulation Configuration" parameter window.
Option "General Purpose": the output relay can be used as a normal binary
output relay controlled by the 1 bit object "Relay OnBoard". In case of "General
Purpose" selection the output can be controlled in normal or timing mode.
Contact
Options:
Normally Open
Normally Close
Option "Normally Open":
Off telegram = contact open
On telegram = contact closed.
.
Option "Normally Close":
Off telegram = contact closed
On telegram = contact open.
Fig. 9: Parameter Window "Relay Configuration" with the "General Purpose" function
associated to the output.
23 di 30