Mode
Option:
Option "On-Off" : the output relay will be switched ON by sending an ON
command and will be switched OFF buy sending an OFF command within the
associated object "Relay OnBoard".
The status of the relay contact is inverted by the parameter setting "Contact"=
"Normally Close".
Option "Timing": enable the time switch function (e.g. staircase lighting function).
When an On telegram is received via the output object, it is routed directly to the
relay. The Off delay that has been assigned starts at the same time. Every
further "1" (ON) that is received before the timer has elapsed, resets the delay
and restarts it. Once the period has elapsed, a "0" is passed to the output. An
Off telegram deletes the Off delay and is immediately routed to the output.
The time for the Off delay is set here. This is calculated from the selected base
"TimeBase" multiplied by the factor "Factor" that is entered here:
T
= TimeBase x Factor
ON
Note: An attempt should always be made to set the required time with the
smallest possible base as the base that is selected here also simultaneously
specifies the maximum timing error.
Time Base
Options:
Factor
Options:
Fig. 10: Timing switching function (e.g. "Staircase Lighting")
Note: please see Outputs timing diagrams in "Application Notes".
Normal
Timing
250ms, 500ms, 1sec, 1min, 1hour
0...2...255