4.2 Parameter Window "Temperature Regulation Configuration"

Parameters concerning the regulation algorithm and the type of HVAC plant
system and the fancoil type are configured here.
This parameter window also provides the temperature adjustment for the
temperature sensor calibration (± 1,5° C) and the hysteresis regulation range for
the two step setpoint control (ON/OFF).
Fig. 3: Parameters Window "Temperature Regulation Configuration".
Temperature Regulation
This parameter is useful to set the regulation algorithm required.
Options:
Option "Regulation ON/OFF": with the switching ON/OFF control the control
value is determined internally according to a two-step algorithm with an
adjustable hysteresis set with the next parameter "Temperature Coefficient
Regulation".
The ON/OFF control is normally used in HVAC plants with small thermal inertia
installed in small environments.
Option "Proportional Band": with proportional regulation the actuator (valve)
assumes positions proportional to deviation between the external measured
temperature and the current setpoint (error). The output control command
depends only to this deviation.
The proportional bandwidth is fixed and handled internally.
Regulation ON/OFF
Proportional Band
Integral Band
Proportional/Integral Band