Communication Objects - Eelectron TM11A01KNX Product Handbook

Inwall room thermostat
Hide thumbs Also See for TM11A01KNX:
Table of Contents

Advertisement

5 Communication Objects

The
EIB/KNX
communication
"EEL_RTH1_10 Room Thermostat" are the following:
Fig. 11:Communication Objects EIB/KNX provided with the application program
(NB: some objects are visible only if enabled by specific parameter setting).).
Nr.
Funzione
0
On/Off
After receiving the object from the bus, the thermostat goes to standby mode (when
receiving 0) or in Comfort mode (when receiving 1).
The fixed temperature Set point is used when passing from Comfort mode to Standby
mode and vice versa. When changing mode, a thermostat that was working in manual
gets to automatic mode.
1
On/Off
After receiving the object from the bus, the thermostat goes in Economy mode (e.g.
"Night mode").
The fixed temperature Set point is used when passing to this mode. When changing
mode, a thermostat that was working in manual gets to automatic mode.
2
On/Off
After receiving the object from the bus, the thermostat goes in Antifreeze mode.
The fixed temperature Set point is used when passing to this mode. When changing
mode, a thermostat that was working in manual gets to automatic mode.
In case the input has been enabled with the function "Windows Switch" as the
antifreeze object is received the thermostat switches OFF the heating/cooling system.
objects
provided
within
Nome
0=Standby / 1=Comfort
Economy
AntiFreeze
the
application
program
Tipo
Flag
EIS1, 1bit
C,R,W,T
DPT 1.001
EIS1, 1bit
C,R,W,T
DPT 1.001
EIS1, 1bit
C,R,W,T
DPT 1.001