Goodman ComfortNet ACVC9 Technical Manual

Goodman ComfortNet ACVC9 Technical Manual

90%-95% gas furnace units
Hide thumbs Also See for ComfortNet ACVC9:

Advertisement

TECHNICAL MANU
TECHNICAL MANU AL
TECHNICAL MANU
TECHNICAL MANU
TECHNICAL MANU
90%-95% Gas Furnace Units
Refer to Service Manual RS6200004 for installation, operation, and troubleshooting information.
All safety information must be followed as provided in the Service Manual.
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
®
US
C
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does
not assume any responsibility for property damage or personal injury due to improper service
procedures performed by an unqualified person.
TM
ACVC9/AMVC95
GCVC9/GMVC95
Copyright ©2009-2010 Goodman Manufacturing
AL
AL
AL
AL
Company, L.P.
RT6612021 Rev. 4
December 2010

Advertisement

loading
Need help?

Need help?

Do you have a question about the ComfortNet ACVC9 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Goodman ComfortNet ACVC9

  • Page 1 TECHNICAL MANU TECHNICAL MANU AL TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU ACVC9/AMVC95 GCVC9/GMVC95 90%-95% Gas Furnace Units • Refer to Service Manual RS6200004 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual.
  • Page 2: High Voltage

    PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. PRODUCT ADDITIONAL AFUE TYPE: 9: 90% FEATURES: MINOR G: Goodman® REVISION 95: 95% N: Natural Gas A: Amana®...
  • Page 3 PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GMVC950453BXAA AMVC950453BXAA GMVC950704CXAA AMVC950704CXAA GMVC950905CXAA AMVC950905CXAA GMVC950905DXAA AMVC950905DXAA GMVC951155DXAA AMVC951155DXAA GCVC90704CXAA ACVC90704CXAA GCVC90905DXAA ACVC90905DXAA GCVC91155DXAA...
  • Page 4: Product Design

    3. Conversion kits for propane gas and high altitude natural mostat wiring. and propane gas operation are available. See High Alti- The GCVC9, GCVC95, GMVC95, AMVC95, ACVC9 and tude Derate chart for details. ACVC95 furnaces are equipped with an electronic ignition 4.
  • Page 5 PRODUCT DESIGN quired due to the natural reduction in the density of both the of time before stepping up to high stage to satisfy the gas fuel and combustion air as altitude increases. The kit thermostat’s call for heat. The delay period prior to stepping will provide the proper design certified input rate within the up can be set at either a fixed 5 minute time delay or a load specified altitude range.
  • Page 6: Component Identification

    COMPONENT IDENTIFICATION Upflow/Horizontal Counterflow /Horizontal 1 Two-Stage Gas Valve 18 Coil Front Cover Pressure Tap 2 Gas Line Entrance (Alternate) 19 Coil Front Cover Drain Port 3 Pressure Switch(es) 20 Drain Line Penetrations 4 Gas Manifold 21 Drain Trap 5 Combustion Air Intake Connection 22 Blower Door Interlock Switch 6 Hot Surface Igniter 23 Inductor (Not All Models)
  • Page 7 PRODUCT DIMENSIONS GMVC95/AMVC95___X*...
  • Page 8 PRODUCT DIMENSIONS GCVC9/ACVC9_____X*...
  • Page 9 PRODUCT DESIGN PRESSURE SWITCH TRIP POINTS AND USAGE CHART NEGATIVE PRESSURE NEGATIVE PRESSURE NEGATIVE PRESSURE NEGATIVE PRESSURE ID BLOWER ID BLOWER COIL COVER COIL COVER WITH FLUE WITH FLUE WITH FLUE WITH FLUE NOT FIRING FIRING NOT FIRING FIRING MODEL TYPICAL SEA LEVEL TYPICAL SEA LEVEL TYPICAL SEA LEVEL...
  • Page 10 PRODUCT DESIGN...
  • Page 11 PRODUCT DESIGN PRIMARY LIMIT Part Number 20162903 20162904 20162905 20162907 20162908 0130F00105 Open Setting (°F) GMVC950453BX* AMVC950453BX* GMVC950704CX* AMVC950704CX* GMVC950905CX* AMVC950905CX* GMVC950905DX* AMVC950905DX* GMVC951155DX* AMVC951155DX* GCVC90704CX* ACVC90704CX* GCVC950714CX* ACVC950714C X* GCVC90905DX* ACVC90905DX* GCVC950915DX* ACVC950915D X* GCVC91155DX* ---- ---- ---- ---- R OLLOUT LIMIT SWITCHES Part N um ber 10123512...
  • Page 12 PRODUCT DESIGN AUXILIARY LIMIT SWITCHES Part Number 10123534 10123535 10123537 10123536 10123533 0130F00038 Open Setting (°F) GMVC950453BX* AMVC950453BX* GMVC950704CX* AMVC950704CX* GMVC950905CX* AMVC950905CX* GMVC950905DX* AMVC950905DX* GMVC951155DX* AMVC951155DX* GCVC90704CX* ACVC90704CX* GCVC 950714CX* ACVC950714CX* GCVC90905DX* ACVC90905DX* GCVC 950915DX* ACVC950915DX* GCVC 911555DX*...
  • Page 13 Coil Matches: A large array of Amana® brand coils are available for use with the GCVC9 and ACVC9 furnaces, in either counterflow or horizontal applications & with GMVC95 and AMVC95 furnaces, in either upflow or horizontal applications. These coils are available in both cased and uncased models (with the option of a field installed TXV expansion device).
  • Page 14 PRODUCT DESIGN Thermostats: ComfortNet™ CTK01A* Thermostat Kit Filters: Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty Upflow Filters Return air filters may be installated at the furnace side and/or bottom return openings.
  • Page 15 PRODUCT DESIGN U PFLOW COOLING A IRFLOW REQU IREMEN T (CFM) 1000 1200 1400 1600 1800 2000 04 53__X* 207* 207* 24 0 07 04__X* 318* 318* 09 05__X* 413* 413* 413* 11 55__X* 437* 437* 437* COUNTER FLOW COOLING A IRFLOW REQU IREMEN T (CFM) 1000 1200 1400...
  • Page 16 FURNACE SPECIFICATIONS GMVC95 MODEL GMVC950453BX* GMVC950704CX* GMVC950905CX* GMVC950905DX* GMVC951155DX* Btuh Input (US) High Fire 46,000 69,000 92,000 92,000 115,000 Output (US) High Fire 44,300 66,900 88,800 88,800 111,100 Btuh Input (US) Low Fire 32,000 48,000 64,000 64,000 80,000 Output (US) Low Fire 30,800 46,400 61,700...
  • Page 17 FURNACE SPECIFICATIONS AMVC95 MODEL AMVC950453BX* AMVC950704CX* AMVC950905CX* AMVC950905DX* AMVC951155DX* Btuh Input (US) High Fire 46,000 69,000 92,000 92,000 115,000 Output (US) High Fire 44,300 66,900 88,800 88,800 111,100 Btuh Input (US) Low Fire 32,000 48,000 64,000 64,000 80,000 Output (US) Low Fire 30,800 46,400 61,700...
  • Page 18 FURNACE SPECIFICATIONS GCVC9 MODEL GCVC90704CX* GCVC90905DX* GCVC91155DX* Btuh Input (US) High Fire 69,000 92,000 115,000 Output (US) High Fire 65,300 86,500 109,000 Btuh Input (US) Low Fire 48,000 64,000 80,000 Output (US) Low Fire 45,000 60,100 77,400 A.F.U.E. 93.0% 92.0% Rated External Static ("...
  • Page 19 FURNACE SPECIFICATIONS GCVC95 M O D E L G C V C 95 0 71 4 CX * G C V C9 5 09 1 5D X * B tu h In p ut (US ) Hig h Fire 69 ,0 0 0 9 2 ,0 00 O u tp ut (US ) Hig h Fire 65 ,3 0 0...
  • Page 20 FURNACE SPECIFICATIONS ACVC9 M O D E L A C V C 9 0 7 0 4 C X * A C V C 9 0 9 0 5 D X * B tu h In p u t (U S ) H ig h F ire...
  • Page 21 FURNACE SPECIFICATIONS ACVC95 M O D E L A C V C9 5 07 1 4C X * A C V C9 50 9 15 D X * B tu h In p ut (U S ) H ig h F ire 69 ,0 0 0 92 ,0 0 0 O u tp ut (U S ) Hig h F ire...
  • Page 22: Blower Performance Specifications

    BLOWER PERFORMANCE SPECIFICATIONS GMVC95/AMVC95 Heating Speed Charts GMVC950453BX* GMVC950704CX* AMVC950453BX* AMVC950704CX* (Rise Range: 30 - 60°F) (Rise Range: 30 - 60°F) Low Stage High Stage Low Stage High Stage Heating Heating Adjust Rise Adjust Rise Speed Speed at .1" - .5" w.c. at .1"...
  • Page 23 BLOWER PERFORMANCE SPECIFICATIONS GMVC95/AMVC95 Heating Speed Charts GMVC950905DX* GMVC951155DX* AMVC950905DX* AMVC951155DX* (Rise Range: 30 - 60°F) (Rise Range: 35 - 65°F) Low Stage High Stage Low Stage High Stage Heating Heating Adjust Rise Adjust Rise Speed Speed at .1" - .5" w.c. at .1"...
  • Page 24 BLOWER PERFORMANCE SPECIFICATIONS GMVC95/AMVC95 High (Single) Stage Cooling Speed Charts GMVC950453BX* GMVC950704CX* GMVC950905CX* AMVC950453BX* AMVC950704CX* AMVC950905CX* Cooling CFM at Cooling CFM at Cooling CFM at Adjus t Adjus t Adjus t Speed .1" - .8" Speed .1" - .8" Speed .1"...
  • Page 25 BLOWER PERFORMANCE SPECIFICATIONS GMVC95/AMVC95 Low Stage Cooling Speed Charts GMVC950453BX* GMVC950704CX* GMVC950905CX* AMVC950453BX* AMVC950704CX* AMVC950905CX* Cooling CFM at Cooling CFM at Cooling CFM at Adjus t Adjus t Adjus t Speed .1" - .8" Speed .1" - .8" Speed .1" - .8" w.c.
  • Page 26 Continuous fan s peed is 30% of furnace m axim um CFM Three continuous fan s peeds are pos s ible with the CTK01AA therm os tat: 30% , 50% , and 70% of furnace m axim um CFM GCVC9/ACVC9 Continuous Fan Speed Chart Continuous Fan Furnace Maximum...
  • Page 27 BLOWER PERFORMANCE SPECIFICATIONS GCVC9/ACVC9 Heating Speed Charts GCVC90704CX* GCVC90905DX* ACVC90704CX* ACVC90905DX* (Rise Range: 30 - 60°F) (Rise Range: 30 - 60°F) Low Stage High Stage Low Stage High Stage Heating Heating Adjust Rise Adjust Rise Speed Speed at .1" - .5" w.c.
  • Page 28 BLOWER PERFORMANCE SPECIFICATIONS GCVC95/ACVC95 Heating Speed Charts GCVC950714CX* GCVC950915DX* ACVC950714CX* ACVC950915DX* (Rise Range: 25 - 55°F) (Rise Range: 25 - 55°F) Low Stage High Stage Low Stage High Stage Heating Heating Adjust Rise Adjust Rise Speed Speed at .1" - .5" w.c. at .1"...
  • Page 29 BLOWER PERFORMANCE SPECIFICATIONS GCVC9/ACVC9 High (Single) Stage Cooling Speed Charts GCVC90704CX* GCVC90905DX* GCVC91155DX* ACVC90704CX* ACVC90905DX* Cooling CFM at Cooling CFM at Cooling CFM at Adjust Adjust Adjust Speed .1" - .8" Speed .1" - .8" Speed .1" - .8" w.c. ESP w.c.
  • Page 30 BLOWER PERFORMANCE SPECIFICATIONS GCVC95/ACVC95 High (Single) Stage Cooling Speed Charts GCVC950714CX* GCVC950915DX* ACVC950714CX* ACVC950915DX* Cooling CFM at Cooling CFM at Adjust Adjust Speed .1" - .8" Speed .1" - .8" w.c. ESP w.c. ESP Minus(-) Minus(-) Normal Normal Plus (+) Plus (+) Minus(-) Minus(-)
  • Page 31 BLOWER PERFORMANCE SPECIFICATIONS Circulator Blower Speed Adjustment Switches Note: There are dual 7-segment LED's adjacent Sw itch Bank : S3 Sw itch Bank : S3 to the selection dipswitches. The airflow rounded DIP Sw itch No. DIP Sw itch No. Cooling Speed to the nearest 100 CFM, is displayed on the dual A djust Taps...
  • Page 32 BLOWER PERFORMANCE SPECIFICATIONS Ramping Profile Note: The multi-speed circulator blower also offers several custom ON/OFF ramping profiles. These profiles may be used to enhance cooling performance and increase comfort level. The ramping profiles are selected using DIP switches 5 and 6.
  • Page 33 PERFORMANCE...
  • Page 34: Wiring Diagrams

    WIRING DIAGRAMS *CVC9/*MVC95_AA HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. 24V HUM. TO 115VAC / 1 Ø /60 HZ POW ER SUPPLY W ITH DISCONNECT DOOR JUNCTION BOX...
  • Page 35 WIRING DIAGRAMS *CVC9/*MVC95_AB HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. 115 VAC/ 1 Ø /60 HZ POWER SUPPLY WITH ID BLOWER TWO-STAGE PRESSURE OVERCURRENT SWITCH ASSEMBLY...
  • Page 36 ANSI Z21.20 AUTOMATIC IGNITION SYSTEM 24VAC 60Hz 0.8 A. MAX. BLOWER ASSEMBLY SCHEMATIC ACVC9/AMVC95/GCVC9/GMVC95_____X* MODEL FURNACES This schematic is for reference only. Not all wiring is as shown above, refer to the appropriate wiring diagram for the unit being serviced.
  • Page 37 SCHEMATICS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.