PRODUCT DESIGN
Thermostats:
ComfortNet™ CTK01A* Thermostat Kit
Filters:
Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or
CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty
Return air filters may be installated at the furnace side and/or bottom return openings. The furnace bottom return opening
and side openings will accommodate the following filter sizes depending on cabinet size:
Cabinet
W idth
(in.)
All
Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in
the duct system such as a central return.
04 53__X*
07 04__X*
09 05__X*
11 55__X*
0704 __X*
0714 __X*
0905 __X*
0915 __X*
11 55__X*
14
Side Re turn Ope ning(s)
Approx.
Nominal
Flow Area
Filter Size
2
(in.)
(in
16 x 25 x 1
400
COOLING A IRFLOW REQU IREMEN T (CFM)
600
800
415*
415*
---
---
---
---
---
---
COOLING A IRFLOW REQU IREMEN T (CFM)
600
800
---
---
---
---
---
---
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter Area (in
[Based on a 300 ft/min filter face velocity]
Upflow Filters
Cabinet
W idth
(in.)
)
17-1/2
21
24-1/2
U PFLOW
1000
1200
1400
48 0
576
---
636*
636*
672
---
826*
826*
---
875*
875*
COUNTER FLOW
1000
1200
1400
634*
634*
672
---
819*
819*
---
860*
860*
Bottom Re turn Ope ning
Approx.
Nominal
Flow Area
Filter Size
(in.)
(in
14 x 25 x 1
350
16 x 25 x 1
400
20 x 25 x 1
500
1600
1800
2000
---
---
---
768
---
---
826*
864
960
875*
875*
960
1600
1800
2000
768
---
---
819*
864
960
860*
864
960
2
)
2
)