Model 1100 Instruction Manual
or low temperature alarm is disabled, the 1100 will say "Off" and then
recite the programmed limit in degrees.
WHAT
6
IS

AC POWER MONITORING ENABLE I DISABLE

The Model 1100 monitors AC power failure. This command enables or
disables the power failure detection feature. When enabled, the Model
1100 will monitor power and dial out if a valid failure occurs (see AC
POWER RECOGNITION TIME below). When disabled, the Model 1100
will not dial out for a power alarm. The default setting is enabled (on).
To enable/disable the AC power alarm:
1. Press the SENSOR ON/OFF key
2. Press the ELECT key
The 1100 will say "Off" to indicate that the power alarm is disabled, or the
1100 will say "On" to indicate that the power alarm is enabled.
3. Repeat key sequence to change.
SENSOR
7
ON/OFF
To interrogate:
1. Press the WHAT IS key
2. Press the ELECT key
If the power alarm is enabled, the 1100 will simply recite the programmed
power recognition time (see below). If the power alarm is disabled, the
1100 will say "Off" and then recite the programmed recognition time.
WHAT
7
IS

AC POWER FAILURE RECOGNITION TIME

The power recognition time is the length of time that a power failure must
exist continuously before the Model 1100 will recognize it as an actual
alarm and start the dialout sequence. The default setting is 100 seconds.
You may program the power recognition time from 1 to 199 seconds.
28