THIS APPLIANCE MUST HAVE ADEQUATE AMOUNT OF AIR FOR PROPER
OPERATION. IF NOT, POOR FUEL COMBUSTION COULD RESULT. READ
FOLLOWING INSTRUCTIONS TO ENSURE PROPER AMOUNT OF AIR FOR THIS
AND OTHER FUEL-BURNING APPLIANCES IN YOUR HOME.

AIR FOR COMBUSTION AND VENTILATION OUTDOORS

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent
openings: one within 12" of ceiling and one within 12" of floor. Connect these items directly to
outdoors. These spaces include attics and crawl spaces. Follow National Fuel Gas Code
NFPA 54/ANSI Z223.1, Section 5.3, "Air For Combustion and Ventilation" for required size of
ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the attic will activate the power unit.
WARNING
Ventilated Attic
Outlet Air
Outlet Air
7" MIN .
C LE A R A N C E
TO S ID E W A LL
S ID E W A LL
Inlet Air
Inlet Air
Ventilation Air From Outdoors
Page 25
To Attic
FIGU R E 4
To
24" MIN .
Crawl
C LE A R A N C E
TO C E ILIN G
Space
Ventilated
Crawl Space