Start-Up And Configuration; Dip Switch Settings Overview; Room Thermostat Installation Configuration; Pump Operation Configuration - Daikin EKHVH008BB6V3 Installation Manual

Daikin altherma indoor unit installation manual
Hide thumbs Also See for EKHVH008BB6V3:
Table of Contents

Advertisement

8.
S
-
TART
UP AND CONFIGURATION
The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user expertise.
ATTENTION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: ELECTRIC SHOCK
See
"2. General safety precautions" on page

8.1. DIP switch settings overview

DIP switch SS2 is located on the switch box PCB (see
box main components" on page
domestic hot water tank installation, room thermostat connection and
pump operation.
WARNING
Switch off the power supply before opening the switch box
service panel and making any changes to the DIP switch
settings.
DIP
switch
SS2
Description
1
Not applicable for installer
2
Domestic hot water tank
installation
(see
"8.4. Domestic hot
water tank installation
configuration" on page
3
Room thermostat
connection
(see
"8.2. Room
thermostat installation
configuration" on page
4
Not applicable. Do not change the default setting.
8.2. Room thermostat installation configuration
When no room thermostat is connected to
the indoor unit, toggle switch SS2-3 should be
set to OFF.
When the room thermostat is connected to
the indoor unit, toggle switch SS2-3 should be
set to ON.
On the room thermostat, confirm the correct settings (6®02=yes,
6®05=9, 6®06=5) to prevent the pump from repeatedly turning on
and off (i.e. chattering), and thereby impacting the lifetime of
the pump.
Installation manual
24
2.
"5.3. Switch
10) and allows configuration of
1
2
3
4
ON
OFF
(Default)
Installed
Not installed
(Default)
25)
Room thermostat
No room
connected
thermostat
connected
(Default)
24)
1
1
When the room thermostat is connected to the indoor
unit, the heating and cooling schedule timers are
never available. Other schedule timers are not
affected. For more information on the schedule timers,
refer to the operation manual.
When the room thermostat is connected to the indoor
unit, and the = button or y button is pressed, the
centralised control indicator e will flash to indicate
that the room thermostat has priority and controls
on/off operation and change over operation.
The following table summarizes the required configuration and
thermostat wiring at the terminal block (X2M: 1, 2, 3, 4) in the switch
box. Pump operation is listed in the third column. The three last
columns indicate whether the following functionality is available on
the user interface (UI) or handled by the thermostat (T):
space heating or cooling on/off (y)
heating/cooling changeover (=)
heating and cooling schedule timers (pr)
Thermostat
No thermostat
Heating only
thermostat
Thermostat with
heating/cooling
switch
(a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature.
8.3. Pump operation configuration
2
3
4
To set the pump speed, refer to
speed" on page
2
3
4
Without room thermostat: DIP switch SS2-3=OFF
When no thermostat is connected to the indoor unit, pump operation
will be determined by the leaving water temperature.
To force continuous pump operation when no room thermostat is
connected do the following:
-
set toggle switch SS2-3 to ON,
-
short-circuit the terminal numbers 1-2-4 on the terminal block
in the switch box.
With room thermostat DIP switch: SS2-3=ON
When the thermostat is connected to the indoor unit, the pump will
operate continuously whenever there is heating or cooling demand
requested by the thermostat.
Dual set point
When dual set point is enabled, the pump operation will be
determined depending on the status of the DIP switch SS2-3 and set
point selection contacts. Refer to the pump operation configurations
when the thermostat is connected or not as described above.
Pump
Configuration
operation
• SS2-3 = OFF
determined by
leaving water
• wiring: (non)
(a)
temperature
X2M
1 2 3 4
• SS2-3 = ON
on when space
heating or
• wiring:
cooling is on
(y)
X2M
1 2 3 4
• SS2-3 = ON
on when
heating
• wiring: (see
request by
installation
room
manual of the
thermostat
room
thermostat kit)
• SS2-3 = ON
on when
heating
• wiring: (see
request or
installation
cooling request
manual of the
by room
room
thermostat
thermostat kit)
"8.7. Setting the pump
26.
EKHVH/X008BB6V3 + EKHVH/X008BB6+9WN
Daikin Altherma indoor unit
y
y
y
y
=
=
=
=
p p p p r r r r
UI
UI
UI
UI
UI
UI
T
T
T
4PW64329-1 – 07.2010