Installation Of The Digital Controller; Wiring Specifications; Start-Up And Configuration; Dip Switch Settings Overview - Daikin Altherma EDHQ011BB6V3 Installation Manual

Unit for to water heat pump system
Hide thumbs Also See for Altherma EDHQ011BB6V3:
Table of Contents

Advertisement

Installation of the digital controller

The unit is equipped with a digital controller offering a user-friendly
way to set up, use and maintain the unit. Before operating the
controller, follow this installation procedure.
Wiring specifications
Wire specification
Type
Section
Maximum length
NOTICE
The wiring for connection is not included.
Procedure
NOTICE
The digital controller, delivered in a kit, has to be mounted
indoors.
1
Remove the front part of the digital controller.
Insert a slotted screwdriver into the slots (1)
in the rear part of the digital controller, and
remove the front part of the digital
controller.
2
Fasten the digital controller on a flat
surface.
NOTICE
Be careful not to distort the shape of the lower part of the
digital controller by over tightening the mounting screws.
3
Wire the unit.
1
1
2
P2
P1
3
4
1 Unit
2 Rear part of the digital controller
3 Front part of the digital controller
4 Wired from the rear
5 Wired from the top
6 Notch the part for the wiring to pass through with nippers,
etc.
Connect the terminals on top of the front part of the digital
controller and the terminals inside the unit (P1 to 16, P2 to 16a).
NOTICE
When wiring, run the wiring away from the power
supply wiring in order to avoid receiving electric
noise (external noise).
Peel the shield for the part that
has to pass through the inside of
the digital controller case ( l ).
E(D/B)(H/L)Q011~016BB
Unit for air to water heat pump system
4PW67904-1 – 01.2011
Value
2 wire
2
0.75~1.25 mm
500 m
1
6
P2
P1
5
4
Reattach the upper part of the digital controller.
CAUTION
Be careful not to pinch the wiring when attaching.
First begin fitting from the clips at the
bottom.
10. S
-
TART
UP AND CONFIGURATION
The unit should be configured by the installer to match the installation
environment (outdoor climate, installed options, etc.) and user
expertise.
CAUTION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: ELECTRIC SHOCK
See
"2. General safety precautions" on page

10.1. DIP switch settings overview

DIP switch SS2 is located on the switch box PCB (see
main components (door 2)" on page
domestic hot water tank installation, room thermostat connection and
pump operation.
WARNING
Switch off the power supply before opening the switch box
service panel and making any changes to the DIP switch
settings.
DIP
switch
SS2
Description
1
Not applicable for installer
2
Domestic hot water tank
installation (see
"10.4. Domestic hot water
tank installation
configuration" on page
3
Room thermostat
connection(see
"10.2. Room thermostat
installation configuration"
on page
29)
(a)
4
This setting
decides the
operation mode when
there is a simultaneous
demand for more space
heating/cooling and
domestic water heating.
(a) Only applicable in case DIP switch 2=ON.
(b) Heating/cooling or domestic water heating mode can be restricted by schedule
timer and/or field settings (4, 5, 8).
2.
"Switch box
11) and allows configuration of
1
2
3
4
ON
OFF
(Default)
Installed
Not installed
(Default)
30)
Room thermostat
No room
connected
thermostat
connected
(Default)
Heating/cooling
Priority to highest
priority
demand side
Installation manual
1
(b)
28