No.
Item
10
DAfter-heat
When heating operation stops, the indoor fan operates with LOW
elimination
mode for approx. 30 seconds.
11
Frequency
<In case of wired remote controller>
fixed
1. When pushing [CHECK] button for 4 seconds or more, [TEST] is displayed on the
operation
display screen and the mode enters in Test run mode.
(Test run)
2. Push [ON/OFF] button.
3. Using [MODE] button, change the mode from [COOL] to [HEAT].
• Do not use other mode than [COOL]/[HEAT] mode.
• During test run operation, the temperature cannot be adjusted.
• An error is detected as usual.
• A frequency fixed operation is performed.
4. After the test run, push [ON/OFF] button to stop the operation. (Display in the display
part is same as the procedure in item 1).)
5. Push [CHECK] button to clear the test run mode.
([TEST] display in the display part disappears and the status returns to the normal stop
status.)
<In case of wireless remote controller>
1. Turn off the power of the set.
Remove the adjuster with sensors from the ceiling panel.
2. Turn Bit [1: TEST] of sensor P .C. board switch [S003] from OFF to ON.
Turn on the power of the set.
3. Push [ON/OFF] button of the wireless remote controller and set the operation mode to
[COOL] or [HEAT] using [MODE] button.
(During test run operation, all the display lamps of wireless remote controller sensors
flash.)
• Do not use other mode than [COOL]/[HEAT] mode.
• An error is detected as usual.
• A frequency fixed operation is performed.
4. After the test run, push [ON/OFF] button to stop the operation.
5. Turn off the power of the set.
Turn Bit [1: TEST] of sensor P .C. board switch [S003] from ON to OFF.
Mount the adjuster with sensors to the ceiling panel.
12
Central
1) Setting at the central controller side enables to select the
control
contents which can be operated on the remote controller at
indoor unit side.
mode
selection
2) RBC-AMT21
[Last push priority] :
The operation contents can be selected from both remote
controller and central controller of the indoor unit side, and the
operation is performed with the contents selected at the last.
[Center] :
Start/Stop operation only can be handled on the remote control-
ler at indoor unit side.
[Operation Prohibited] :
It cannot be operated on the remote controller at indoor unit
side. (Stop status is held.)
Outline of specifications
– 83 –
www.ilmalämpöpumput.com
RAV-SM561/801/1101/1401CT-E
Remarks
(No display)
[CENTER] goes on.
[CENTER] goes on.
In a case of wireless
type, the display lamp
does not change.
However, contents which
can be operated are
same.
The status set in [CEN-
TER]/[Operation Prohib-
ited] mode is notified with
the receiving sound "Pi,
Pi, Pi, Pi, Pi" (5 times).