Toshiba RAV-SP560AT-E Service Manual page 42

Hide thumbs Also See for RAV-SP560AT-E:
Table of Contents

Advertisement

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
RAV-SM1401CT-E, RAV-SP1400AT-E (A03-014)
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
15.9mm
9.5mm
TD sensor
Accumulator
Rotary
(2500cc)
compressor
(DA420A3F – 21M)
Pressure
(MPa)
Pd
Standard
2.76
Cooling
Overload
3.46
Low load
1.77
Standard
2.65
Heating
Overload
3.33
Low load
2.50
4 poles are provided to this compressor.
*
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Refrigerant pipe
at gas side
Outer dia. ØA
Ball valve
Outer dia. ØA
Strainer
TS sensor
Check joint
4-way valve
(STF-0401G)
Heat exchanger
Muffler
2 row 52 stages
Outside :
Ø25 × L210
Ø8 FP1.3 flat fin
Inside :
Ø25 × L180
Ø9.52 FP1.5 flat fin
Pipe surface temperature (°C)
Discharge
Suction
Ps
(TD)
(TS)
0.91
74
11
1.03
82
17
0.78
48
9
0.69
75
3
1.08
74
19
0.22
98
–22
www.ilmalämpöpumput.com
Indoor unit
TCJ sensor
Strainer
Air heat exchanger
Outdoor unit
TO sensor
TE sensor
Indoor heat Outdoor heat
exchanger
exchanger
(TC)
(TE)
9
39
16
48
6
27
43
3
55
15
43
–18
– 42 –
RAV-SM1401CT-E
RAV-SP1400AT-E
Distributor
(Strainer incorporated)
TC sensor
Refrigerant pipe
at liquid side
Outer dia. ØB
Packed valve
Outer dia. ØB
PMV
(UKV-25D22)
Strainer
Distributor
R410A 2.95kg
Indoor/Outdoor
Compressor
temp. conditions
Indoor
revolutions per
(DB/WB) (°C)
fan
second (rps)
*
Indoor
53
HIGH
27/19
51
HIGH
32/24
24
LOW
18/15.5
55
HIGH
20/–
24
LOW
30/–
73
HIGH
15/–
Min.
Max.
5m
70m
Cooling
Heating
Outdoor
35/–
43/–
–5/–
7/6
24/18
–15/
(70%)