Toshiba RAV-SP560AT-E Service Manual page 157

Hide thumbs Also See for RAV-SP560AT-E:
Table of Contents

Advertisement

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
12-1-4. Monitor Function of Remote Controller Switch
n Call of sensor temperature display
<Contents>
Each sensor temperature of the remote controller, indoor
unit, and outdoor unit can become known by calling the
service monitor mode from the remote controller.
<Procedure>
1
Push
+
buttons simultaneously for 4
seconds or more to call the service monitor
mode.
The service monitor goes on, the master indoor unit
No. is displayed, and then temperature of the item
00
code
is displayed.
2
Push the temperature setup
to select the sensor No. (Item code) of the sensor
to be monitored.
The sensor numbers are described below:
Item code
00
01
Indoor
02
unit data
03
04
*1 Only master unit in group control
3
The temperature of indoor units and outdoor unit in a group control can be monitored by pushing
button to select the indoor unit to be monitored.
4
Pushing
button returns the display to usual display.
/
buttons
Data name
Room temp (under control) *1
Room temp (remote controller)
Indoor suction temp
Indoor coil temp (TCJ)
Indoor coil temp (TC)
– 157 –
www.ilmalämpöpumput.com
SET DATA
4
SET
1
<Operation procedure>
1
2
Item code
60
Heat exchanger temp TE
61
Outside temp TO
Outdoor
62
Discharge temp TD
unit data
63
Suction temp TS
64
65
Heat sink temp THS
All Models
UNIT No.
R.C.
No.
UNIT
CL
3
3
4
Returned to usual display
Data name
2