10-2. Check Code List

Wireless sensor
Wired remote
lamp display
controller
Operation Timer
Ready
Check code
E03
No communication from remote controller (including wireless)
and communication adapters
E04
The serial signal is not output from outdoor unit to indoor unit.
• Miscabling of inter-unit cables
• Defective serial sensing circuit on outdoor P .C. board
• Defective serial receiving circuit on indoor P.C. board
E08
Duplicated indoor unit addresses
L03
Duplicated indoor master units
L07
There is group line in individual indoor units.
L08
Unsetting of indoor group address
L09
Unset indoor capacity
L30
Abnormal outside interlock input
P01
Fan motor thermal protection
P10
Float switch operation
• Disconnection, coming-off, defective float switch contactor
of float circuit
P12
Indoor DC fan error
P19
Error in 4-way valve system
• Indoor heat exchanger temperature lowered after start of
heating operation.
P31
Own unit stops while warning is output to other indoor units.
F01
Coming-off, disconnection or short of indoor heat exchanger
sensor (TCJ)
F02
Coming-off, disconnection or short of indoor heat exchanger
sensor (TC)
F10
Coming-off, disconnection or short of indoor heat exchanger
sensor (TA)
F29
Indoor EEPROM error
• EEPROM access error
E10
Communication error between indoor MCU
• Communication error between fan driving MCU and main
MCU
E18
Regular communication error between master and sub indoor
units or between main and sub indoor units
Error mode detected by indoor unit
Diagnostic function
Status of air
Cause of operation
conditioner
Stop
(Automatic reset)
S top
(Automatic reset)
Stop
Stop
Stop
Stop
Stop
Stop
Stop
(Automatic reset)
Stop (Sub unit)
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
www.ilmalämpöpumput.com
Judgment and measures
Condition
Displayed when
1. Check cables of remote controller and communication adapters.
error is detected
• Handy remote controller LCD display OFF (Disconnection)
• Central remote controller [97] check code
Displayed when
1. Outdoor unit does not completely operate.
error is detected
• Inter-unit cable check, correction of miscabling, case thermo operation
• Outdoor P .C. board check, P.C. board cables check
2. In normal operation
P .C. board (Indoor receiving/Outdoor sending) check
Displayed when
1. Check whether there is modification of remote controller connection (Group/
error is detected
Individual) or not after power has been turned on (finish of group configuration/
address check).
* If group configuration and address are not normal when the power has been turned
on, the mode automatically shifts to address setup mode. (Resetting of address)
Displayed when
1. Set the indoor capacity. (DN=I1)
error is detected
Displayed when
1. Check outside devices.
error is detected
2. Check indoor P .C. board.
Displayed when
1. Check thermal relay of fan motor.
error is detected
2. Check indoor P .C. board.
Displayed when
1. Defect of drain pump
error is detected
2. Clogging of drain pump
3. Check float switch.
4. Check indoor P .C. board.
Displayed when
1. Defective detection of position
error is detected
2. Over-current protective circuit of indoor fan driving unit operates.
3. Lock of indoor fan
4. Check indoor P .C. board.
Displayed when
1. Check 4-way valve.
error is detected
2. Check indoor heat exchanger (TC/TCJ) sensor.
3. Check indoor P .C. board.
Displayed when
1. Judge sub unit while master unit is in [E03], [L03], [L07], [L08].
error is detected
2. Check indoor P .C. board.
Displayed when
1. Check indoor heat exchanger temperature sensor (TCJ).
error is detected
2. Check indoor P .C. board.
Displayed when
1. Check indoor heat exchanger temperature sensor (TC).
error is detected
2. Check indoor P .C. board.
Displayed when
1. Check indoor heat exchanger temperature sensor (TA).
error is detected
2. Check indoor P .C. board.
Displayed when
1. Check indoor EEPROM. (including socket insertion)
error is detected
2. Check indoor P .C. board.
Displayed when
1. Check cables of remote controller.
error is detected
2. Check power cables of indoor unit.
3. Check indoor P .C. board.
Displayed when
1. Check cables of remote controller.
error is detected
2. Check indoor power cable.
3. Check indoor P .C. board.
: Flash,
: Go on,
: Go off