Toshiba RAV-SP560AT-E Service Manual page 82

Hide thumbs Also See for RAV-SP560AT-E:
Table of Contents

Advertisement

Toshiban lämmitys- ja jäähdytyslaitteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
Item
7
Freeze preven-
1) The cooling operation (including Dry operation) is
tive control
(Low tempera-
ture release)
8
High-temp
1) The heating operation is performed as follows based on
release control
Setup at
shipment
NOTE :
When the operation has started or when Tc or Tcj became
lower than 30°C after start of the operation, temperature is
controlled between values in parentheses of A and B.
9
Drain pump
1) In cooling operation (including Dry operation), the drain
control
2) If the float switch operates while drain pump operates,
When, the
drain up kit
(sold sepa-
3) If the float switch operates while drain pump stops, the
rately) is
mounted.
Outline of specifications
performed as follows based on the detected tempera-
ture of Tc sensor or Tcj sensor.
When [J] zone is detected for 6 minutes (Following
figure), the commanded frequency is decreased from
the real operation frequency. After then the commanded
frequency changes every 30 seconds while operation is
performed in [J] zone.
In [K] zone, time counting is interrupted and the opera-
tion is held.
When [I] zone is detected, the timer is cleared and the
operation returns to the normal operation.
If the commanded frequency becomes S0 because the
operation continues in [J] zone, the return temperature
A is raised from 5°C to 12°C until [I] zone is detected
and the indoor fan operates with [M] mode.
(˚C)
5
I
2
In heating operation, the freeze-preventive control
works if 4-way valve is not exchanged and the condition
is satisfied. (However the temperature for J zone
dashing control is changed from 2°C to –5°C.)
the detected temperature of Tc sensor or Tcj sensor.
• When [M] zone is detected, the commanded fre-
quency is decreased from the real operation fre-
quency. After then the commanded frequency
changes every 30 seconds while operation is per-
formed in [M] zone.
• In [N] zone, the commanded frequency is held.
• When [L] zone is detected, the commanded fre-
quency is returned to the original value by approx.
6Hz every 60 seconds.
Control temp (°C)
A
B
56 (54)
52 (52)
pump is usually operated.
the compressor stops, the drain pump continues the
operation, and a check code is output.
compressor stops and the drain pump operates. If the
float switch keeps operating for approx. 4 minutes, a
check code is output.
www.ilmalämpöpumput.com
A
K
J
Tc
(˚C)
Tcj
A
B
L
– 82 –
RAV-SM561/801/1101/1401CT-E
Remarks
Tcj : Indoor heat ex-
changer sensor
temperature
[M] mode :
Air speed selection
M
N
Same when thermostat is
turned off.
Check code [P10]