10-4-4. Check Code Table
RAV-SM1100UT-E, RAV-SM1400UT-E, RAV-SM1100AT-E, RAV-SM1400AT-E (A03-003)
Operation of diagnostic function
Block
Check
display
code
[MODE]
The serial signal is not output
[TIMER] lamp
from outdoor unit to indoor unit.
5Hz flash
• Miscabling of inter-unit cables
• Defective serial sending
• Defective serial receiving
• Compressor case thermo
BUS communication circuit error
* BUS communication was
Network address miss-setting
• Addresses of central
Error in 4-way valve system
• Indoor heat exchanger
• Indoor heat exchanger
Error in other cycles
• Indoor heat exchanger temp
*
[MODE] lamp
Coming-off, disconnection or
5Hz flash
short of indoor temp sensor
(TA)
Coming-off, disconnection or
short of indoor temp sensor
(TC)
Coming-off, disconnection or
short of indoor temp sensor
(TCJ)
: No display in the setting at shipment
*
Error mode detected by indoor unit (1)
Cause of operation
circuit on outdoor P.C. board
circuit on outdoor P.C. board
operation
interrupted over the specified
time.
controllers (Central control
remote controller, etc.) are
duplicated.
temperature rise after start of
cooling operation.
temperature fall after start of
heating operation.
(TC) does not vary after start
of cooling/heating operation.
www.ilmalämpöpumput.com
Status of air
Condition
conditioner
Operation
Displayed when
continues
error is detected
Operation
Displayed when
continues
error is detected
(According
to remote
controller of
indoor unit)
Operation
Displayed when
continues
error is detected
Operation
Displayed when
continues
error is detected
Operation
Displayed when
continues
error is detected
Operation
Displayed when
continues
error is detected
Operation
Displayed when
continues
error is detected
Operation
Displayed when
continues
error is detected
– 143 –
RAV-SM1100/1400UT-E
RAV-SM1100/1400AT-E
Judgment and measures
1. Outdoor unit does not completely
operate.
• Inter-unit cable check, correction of
miscabling
• Outdoor P.C. board check, P.C. board
cables check
• Compressor case thermo check
2. In normal operation
When outdoor sending serial LED
(Green) flashes, the receiving serial
LED (Orange) also flashes. : Indoor
P.C. board (Main P.C. board) check
When the receiving serial LED
(Orange) does not flash: Outdoor P.C.
board check
1. Communication line check, miscabling
check
Power supply check for central
controller (Central control remote
controller, etc.) and indoor unit
2. Communication check (XY terminal)
3. Indoor P.C. board check
4. Central controller check
(Communication P.C. board)
1. Check central control system network
address setting. (SW02)
2. Indoor P.C. board check
3. Central controller check
(Communication P.C. board)
1. Check 4-way valve.
2. Check 2-way valve and non-return
valve.
3. Check indoor heat exchanger sensor
(TC).
4. Check indoor P.C. board (Main P.C.
board).
1. Compressor case thermo operation
2. Coming-off of detection part of indoor
heat exchanger sensor
3. Check indoor heat exchanger sensor
(TC).
4. Check indoor P.C. board (Main P.C.
board).
1. Check indoor temp sensor (TA).
2. Check indoor P.C. board (Main P.C.
board).
1. Check indoor temp sensor (TC).
2. Check indoor P.C. board (Main P.C.
board).
1. Check indoor temp sensor (TCJ).
2. Check indoor P.C. board (Main P.C.
board).