Technical Data

11 Technical Data
PV generator connection data
Max. input voltage
Input voltage, MPP range
PV start voltage, adjustable
Max. input current
Max. input power
Voltage ripple
Internal consumption during
operation
a)
The maximum open circuit voltage, which can occur at a cell temperature of 10 °C, may not exceed the maximum input
voltage.
Grid connection data
Nominal output power
Peak output power
Nominal output current
Max. output current
Max. fuse protection
Harmonic distortion of output current
(at K
< 2 %, P
Ugrid
AC
Short Circuit Proof
Nominal operating voltage
Voltage range
(extended operating range)
Nominal operating frequency
Frequency range
(extended operating range)
Power factor (at nominal output
power)
Overvoltage category
Test voltage (DC)
Test surge voltage
Internal consumption in night
operation
42
SB11_12_17-IEN094131
U
DC Max
U
PV
U
PV Start
I
PV Max
P
DC
U
PP
P
AC nom
P
AC max
I
AC nom
I
AC max
K
IAC
> 0.5 P
)
ACnom
U
AC nom
U
AC
f
AC nom
f
AC
cos ϕ
SB 1100
SB 1200
400 V
139 V ... 320 V 100 V ... 320 V 139 V ... 320 V
180 V
10 A
12.6 A
1210 W
1320 W
< 10 % of the input voltage
< 4 W
(standby)
(standby)
SB 1100
SB 1200
1000 W
1200 W
1100 W
1200 W
4.4 A
5.6 A
grid-side via current regulation
220 V / 230 V / 240 V
180 V ... 260 V
50 Hz / 60 Hz
50 Hz: 45.5 Hz ... 54.5 Hz
60 Hz: 55.5 Hz ... 64.5 Hz
1.7 kV (1 s routine testing / 5 s type testing)
4 kV (serial interface: 6 kV)
SMA Solar Technology AG
SB 1700
a)
120 V
180 V
12.6 A
1850 W
< 4 W
< 5 W
(standby)
SB 1700
1550 W
1700 W
5.2 A
6.7 A
6.1 A
8.6 A
16 A
< 3 %
1
III
0.1 W