5.2 Connecting the Sunny Boy to the public grid (AC)
Connection requirements of the grid operator
Comply with the connection requirements of your utility operator.
Cable Design
The conductor cross-section should be dimensioned in a way that output losses do not exceed 1% at
nominal power. Use "Sunny Design" (www.SMA.de/en/SunnyDesign) for this.
The maximum cable lengths relative to the conductor cross-section are shown in the following table.
Conductor cross-section
1.5 mm²
2.5 mm²
The conductor cross-section required in individual cases depends on the following factors:
• ambient temperature,
• routing method,
• UV resistance,
• line losses,
• valid installation guidelines of the respective country (of the installation site).

Cable Requirements

Position
A
B
C
Installation Guide
SB 1100
21 m
35 m
Designation
External diameter
Conductor cross-section
Strip insulation
Maximum cable length
SB 1200
18 m
30 m
Value
9 ...17 mm
max. 2.5 mm²
4 ... 5 mm
SB11_12_17-IEN094131
Electrical Connection
SB 1700
15 m
22.5 m
17