INTRODUCTION
INTRODUCTION
Today's sophisticated electronic equipment requires reliable surge protective devices. By selecting Joslyn
Solutions
, TransTrack
devices, you have taken a critical step toward decreasing downtime and ensuring longer product life
™
™
for your equipment.
TransTrack is designed to protect facilities and sensitive electrical and electronic equipment against the harmful effects of
lightning strikes and internally generated electrical transients. These reliable surge protection devices fulfill the single-pulse
surge current capacity testing recommendations per NEMA LS-1, 1992, sections 2.2.9 and 3.9.
TransTrack combines easy installation with many special features to deliver more performance than any other device in its
class.
TransTrack is conveniently pre-wired with 24-inch, stranded #10 AWG pigtail conductors. To ensure optimum product
performance, install your TransTrack system in a location that minimizes wire lengths and wire bends. This positioning
maximizes surge suppression and filtering while providing added protection for the connected loads.
WARNING: HAZARDOUS VOLTAGES PRESENT Improper installation or misapplication may result in
serious personnel injury and/or damage to electrical system. Read the complete installation instructions before
!
proceeding with installation. Remove all power to the electrical panel before installing or servicing the
suppressor.
IMPORTANT SAFETY INSTRUCTIONS All work must be performed by licensed and qualified personnel. The electrical
system must be properly grounded in accordance with the U.S. National Electrical Code, state and local codes or other
applicable codes for this suppressor to function properly. Do not connect TransTrack to the line side of the main service
breaker or disconnecting means. This device is suitable for installation where the available short circuit current is
65,000 RMS symmetrical amperes at 480VAC or less.
™
TRANSTRACK
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
STRIPE COLOR
MODULE TYPE
®