Suffixes shown at the end of model number denote available options Option Suffixes Notes: The power system operation frequency is between 47-63 HZ Denotes surge rating per phase 080, 120, 160, 200, 240, 300, or 400 For surge counter Confirm that the environmental conditions are consistent with For non-fused disconnect...
WARNING: Check to ensure that a proper bond is installed between neutral and ground at the transformer upstream from all 3-phase WYE, 3-phase high leg DELTA or split-phase ServiceTrack ST SPD (See NEC Article 250). If the transformer is not accessible, check the main service disconnect/panel for the N-G bond. Lack of a proper bond will damage ServiceTrack ST and void the warranty.
One or two twists or braids of all conductors per foot and securely tie-wrap when conductor lengths must exceed 12”. 5. Conductor Sizing Total Protection Solutions recommends installing ServiceTrack ST by using the following conductor sizes for phase, ground and neutral connections.
Page 6
Fig. 6 Conduit Openings and Enclosure/Mounting Dimensions "A" TOP VIEW Ø 0.31 (7.9) TYP COVER ENCLOSURE BODY CONDUIT FITTING HOLE "A" "A" LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW STANDARD UNITS CONDUIT FITTING OVERALL DIMENSIONS - IN (mm) MOUNTING HOLES TRADE SIZE PUNCH LOCATIONS SURGE RATING...
Conduit Openings The 80kA unit comes with a 3/4” conduit hub. This hub requires a 1- 1/8” diameter hole for proper installation. The 120kA to 160kA units come with a 1”conduit hub. This hub requires a 1-11/32” diameter hole for proper installation. The 200kA to 400kA units come with a 1.25”...
Install SPD directly adjacent to the point of termination to insure conductor length is as short as possible for optimum performance and protection. 2. Connecting Form C Dry Contacts All ServiceTrack ST units come standard with one set of Form “C” dry relay contacts for the SPD status. These contacts are for connection to a user-provided remote alarm and monitoring circuit.
3. Neutral to Ground Filter Jumper All ServiceTrack ST models with enhanced transient filter, “-F” suffix, (which have a neutral connection) come with a green jumper wire, which loops out of the epoxy and connects the filter from neutral to ground. In certain medical applications or circuits which employ or contain Ground Fault Circuit Interrupting protection, this Neutral to Ground filter connection should be removed to avoid any nuisances that may trip the breaker.
(installation labor and site preparation excluded). Return the defective parts within 30 days of receiving the replace- ment. Failure to return the defective parts will result in billing for the replacement parts. To help expedite the return proce- dures, please have the following information at hand when you contact Total Protection Solutions: INFORM TION...
Page 11
Warranty period begins from date of original owner purchase. This warranty is not transferable and may only be enforced by the original end user. Claims under this warranty must be submitted to Total Protection Solutions within thirty (30) days of discovery of any suspected product defect.