5.6

Setup Mode Selection Block Diagram

This section is provided to aid the operator in making selections during the Setup Mode.
It is recommended that the operator fill-in the selections in the proper blanks and then
use this page as a reference while programming the Model TA102A. The blocks shown
below indicate the order of options in the Setup Mode. To the right of each block is a
description of the choices that are available for that option. More information about
making each selection is provided in Section 5.4.
Password
Enter the Password, if the Password is enabled.
Inhibit
Enter the Inhibit Mode, if desired.
Mode ?
Set the Energized (En) / De-Energized (dE) Option
A2 Alarm
Set the Latching (LA) / Non-Latching (nL) Option
Options
Set the A2 alarm set point (from 10 to 60, in increments of 5)
Set the Energized (En) / De-Energized (dE) Option
A1 Alarm
Set the Latching (LA) / Non-Latching (nL) Option
Options
Set the A1 alarm set point (from 10 to 60, in increments of 5)
The A1 Set Point cannot be higher than the A2 Set Point
Calibration
Set the calibration level, LEL (from 25 to 90, in increments of 1)
Level
Fault/Inhibit
Set the Fault Activate (Ac) or not (nA) during Inhibit Mode
Options
Display will indicate "ct" for 5 seconds
Card Test
Set the ramp time for the Card Test Mode (3 or 10 seconds)
Options
Set the Alarm outputs for Active (Ac) or not Active (nA)
Set the Password to be Disabled (Pd) or Enabled (PE)
Password
If the Password is Enabled:
Options
After all of the options have been selected, the TA102A will enter the Setup
Setup
Check Mode.
Check Mode
Set the password digits
35
Model TA102A