Fault/Inhibit Option; Figure 55 - A1 Set Point Option - General Monitors TA102A Instruction Manual

Zero two series trip amplifier module for combustible gas applications
Table of Contents

Advertisement

The last A1 alarm option to appear on the display will be the alarm set point (trip level).
If this level is reached or exceeded the A1 alarm outputs will activate. The display will
indicate the current A1 alarm set point (Figure 55). Press the Mode/Select switch
repeatedly, until the desired A1 alarm set point appears on the display (10 to the A2 set
point in increments of 5). The A1 set point cannot be set higher than the A2 set point. 30
is the factory default for this selection.

5.4.6 Fault/Inhibit Option

Next, the user will select the Fault/Inhibit option. The FAULT LED on the front panel will
be flashing while the display indicates Ac or nA (Figure 57). An Ac selection specifies
that the Model TA102A will activate the Fault circuit while the unit is in the Inhibit Mode.
A nA selection specifies that the Model TA102A will not activate its Fault circuit when
the unit is placed in the Inhibit Mode. A nA selection will not disable the Fault circuit,
therefore, if a Fault occurs during the Inhibit Mode, the unit will activate the Fault
circuit. Not Active is the factory default for this selection.
TA102A
ALARM SETPOINT
0 - 100% LEL
FLASHING A1 LED
A1
READY
SETUP LED
SETUP
FLASHING for SETUP
CHECK MODE,
STEADY for SETUP MODE
MODE/
SELECT
GENERAL
MONITORS
Figure 55 – A1 Set Point Option
30
Model TA102A