Outdoor Water Heaters; Combustion Air (Indoor Units Only) Air For Combustion And Ventilation - Raypak 133 Installation & Operating Instructions Manual

Hot water supply heaters
Table of Contents

Advertisement

Outdoor Water Heaters

These heaters are design certified for outdoor installa-
tion. Heaters must not be installed under an overhang
of less than three (3) feet from the top on the heater.
Three (3) sides must be open in the area under the
overhang. Roof water drainage must be diverted away
from the heaters installed under overhangs with the
use of gutters.
The point from where the flue products exit the heater
must be a minimum of four (4) feet below, four (4) feet
horizontally from or one (1) foot above any door, win-
dow or gravity inlet to a building. The top surface of the
heater shall be at least three (3) feet above any forced
air inlet, or intake ducts located within ten (10) feet hor-
izontally.
Fig. 3: Outdoor Clearances from Openings
High Wind Conditions (Outdoor
Units Only)
In areas where high winds are frequent, it may be nec-
essary to locate the heater a minimum of 3' from high
vertical walls, or install a wind break so the heater is
not in direct wind current.
Combustion Air (Indoor Units
Only) Air for Combustion and
Ventilation
The heater must have both combustion and ventilation
air. Minimum requirements for net free air supply
openings are 12 inches from ceiling for ventilation and
12 inches from the floor for combustion air as outlined
in ANSI Z223.1, and any local codes that may have
jurisdiction.
CAUTION:
Combustion
contaminated by corrosive chemical fumes which
can damage the heater. Measures must be taken to
prevent the entry of corrosive chemical fumes to the
combustion and ventilation air supply. Such
chemicals include, but are not limited to, chlorinated
and/or fluorinated hydrocarbons such as found in
refrigerants, aerosol propellants, dry-cleaning fluids,
degreasers, and paint removers. Other harmful
elements may come from bleaches, air fresheners,
or mastics. Vapors from these types of products can
form corrosive acid compounds when burned in a
gas flame. The resulting acidic condensate can
damage or substantially reduce the life of the heater.
It may become necessary to provide outside air
directly to the heater in order to avoid this problem.
a. All Air From Inside The Building:
Each opening shall have a minimum net free square
inches as noted:
Square
Inches
Model
0133
136
0182/0181
181
0260/0261
264
0330/0331
334
0400/0401
399
0514
512
0624
627
0724
726
0824
825
0962
962
1125
1125
BOLD TYPE indicates Low NOx models.
Table E: All Air From Inside The Building
b. All Air From Outdoors:
When air is supplied directly from outside of building,
each opening shall have a minimum net free square
inches as noted:
Square
Inches
Model
0133
34
0182/0181
46
0260/0261
66
0330/0331
84
0400/0401
100
0514
128
0624
157
0724
182
0824
207
0962
241
1125
282
BOLD TYPE indicates Low NOx models.
Table F: All Air From Outdoors
12
air
must
not
be
Square
Inches
Model
1223
1223
1336
1337
1468
1467
1631
1630
1826
1826
2100
2100
2500
2499
3001
3000
3500
3500
4001
4000
Square
Inches
Model
1223
306
1336
335
1468
367
1631
408
1826
457
2100
525
2500
625
3001
750
3500
875
4001
1000