Piping-Domestic Hot Water Supply Heaters - Raypak 133 Installation & Operating Instructions Manual

Hot water supply heaters
Table of Contents

Advertisement

MODELS
Indoor
Outdoor
T
0133
0133
22
0182/0181
0182
15
0260/0261
0260
21
0330/0331
0330
27
0400/0401
0400
30
0514
0514
20
0624
0624
25
0724
0724
29
0824
0824
30
0962
0926
30
1125
1083
30
1223
1178
30
1336
1287
30
1468
1414
30
1631
1571
30
1826
1758
33
2100
N/A
30
2500
N/A
30
3001
N/A
30
3500
N/A
30
4001
N/A
33
BOLD TYPE indicates Low NOx models.
ΔT = Temperature Rise, Degree F@GPM FLOW
GPM = Gallons per Minute Flow
ΔP = Pressure Drop, Foot thru Heat Exchanger
MPS = Minimum Pipe Size, NPT
SHL = System Head Loss
* Must utilize optional cupro-nickel tubes. If over 25 grains per gallon, a water softener/treatment system must be utilized.
Table I: General Specifications Uni-Temp 80 Hot Water Supply Systems
Piping—Domestic Hot Water
Supply Heaters
Table I above provides data for selecting in-line pumps
for use in a Uni-Temp 80 system for a single heater
and tank according to the following:
1. Flow rates are based on water hardness as meas-
ured in grains per gallon.
Soft: 0-4 grains per gallon.
Medium: 5-15 grains per gallon.
Hard: 16-25 grains per gallon.
2. Maximum Flow Rates:
0133
22 GPM
0181-0401
45 GPM
0514-1826
90 GPM
2100-4001
200 GPM
3. Pressure drop values (ΔP and SHL) and minimum
pipe sizes are for two-pass heaters.
4. Sizing based on heater and tank being placed 5
feet apart. The equivalent length of pipe, valves
and fittings in the system is as follows:
S
O
F
T
0-4 Grains Per Gallon
GPM
P
MPS
SHL
10
3.4
1-1/4
5.1
20
1.8
1-1/2
4.6
20
1.9
1-1/2
4.6
20
1.9
1-1/2
4.7
22
2.3
1-1/2
5.6
42
2.0
2
4.8
41
2.0
2
4.7
41
2.1
2
4.9
45
2.6
2
5.9
53
3.8
2-1/2
5.3
61
5.5
2-1/2
7.5
67
7.0
2-1/2
9.3
73
8.7
2-1/2
11.5
80
11.0
2-1/2
14.4
90
14.8
2-1/2
19.0
90
15.4
2-1/2
19.6
115
5.0
3
7.9
137
7.5
3
11.4
164
11.2
3
17.0
191
16.2
3
23.7
200
18.7
3
26.8
WATER HARDNESS
M
E
D
U I
M
5-15 Grains Per Gallon
T
GPM
P
MPS
17
13
5.5
1-1/4
12
26
3.1
1-1/2
17
26
3.1
1-1/2
21
26
3.2
1-1/2
25
26
3.3
1-1/2
16
52
3.0
2
19
54
3.4
2
20
60
4.4
2
20
68
6.0
2
20
79
8.5
2-1/2
20
90
12.0
2-1/2
22
90
12.5
2-1/2
24
90
13.3
2-1/2
27
90
14.0
2-1/2
30
90
14.8
2-1/2
33
90
15.4
2-1/2
20
172
11.0
3
20
200
15.8
3
25
200
16.7
3
29
200
17.5
3
33
200
18.7
3
1-1/2" NPT = 70 Ft (0181-0401)
2" NPT = 75 Ft (0514-0824)
2-1/2" NPT = 80 Ft (0926-1826)
3" NPT = 85 Ft (2100-4001)
Additional pipe fittings will increase the system
head loss.
5. Select a pump based on the water hardness, flow,
and system head loss.
6. If heater is more than two stories above the tank,
consult the factory.
NOTE: GPM flow rates are limited by maximum
acceptable velocity through heat exchanger tubes.
Heater models 0514 through 1826 may be provided
with an integral rear-mounted pump. This must be
specified at time of order.
MINIMUM INPUT ADJUSTMENT: Model Types WH
have minimum input ratings as specified on their indi-
vidual rating plates. Minimum input controllers have
been pre-set at the factory. Consult with factory repre-
sentatives if a minimum input problem should occur.
23
H
A
R
D
16-25 Grains Per Gallon*
SHL
T
GPM
P
8.2
10
22
14.7
7.5
7
45
9.2
7.6
10
45
9.4
7.7
12
45
9.6
7.8
15
45
9.8
7.1
9
90
9.0
7.9
11
90
9.5
9.8
13
90
10.0
12.8
15
90
10.5
11.5
18
90
11.0
16.2
20
90
12.0
16.7
22
90
12.5
17.5
24
90
13.3
18.2
27
90
14.0
19.0
30
90
14.8
19.6
33
90
15.4
17.2
17
200
14.8
23.9
20
200
15.8
24.8
25
200
16.7
25.6
29
200
17.5
26.8
33
200
18.7
MPS
SHL
1-1/4
22.0
1-1/2
20.8
1-1/2
21.0
1-1/2
21.2
1-1/2
21.3
2
19.1
2
20.9
2
21.4
2
21.9
2-1/2
15.2
2-1/2
16.2
2-1/2
16.7
2-1/2
17.5
2-1/2
18.2
2-1/2
19.0
2-1/2
19.6
3
22.9
3
23.9
3
24.8
3
25.6
3
26.8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents