Plumbing

General
Heater should be located so that any water leaks will
not cause damage to any adjacent areas or structures.
Gas Supply Connections
Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve locat-
ed outside the heater jacket. All gas piping should be
tested after installation in accordance with local codes.
Fig. 19: Sediment Trap
CAUTION: The heater and its manual shut-off
valve must be disconnected from the gas supply
during any pressure testing of that system at test
pressures in excess of 1/2 PSIG. Dissipate test
pressure in the gas supply line before reconnecting
the heater and its manual shut-off valve to gas
supply
line.
FAILURE
PROCEDURE MAY DAMAGE THE GAS VALVE.
OVER PRESSURED GAS VALVES ARE NOT
COVERED BY WARRANTY. The heater and its gas
connections shall be leak tested before placing the
appliance in operation. Use soapy water for leak test
do NOT use open flame.
NOTE: Do not use teflon tape on gas line pipe
thread. A flexible sealant approved for the fuel being
used is recommended.
CAUTION: For proper operation, no more than a
30% drop in gas supply pressure from no-load to full-
load
conditions
circumstances should the pressure be outside the
listed operational range.