Symptom
4
"88" appears on re-
[Generates at registration and confirmation]
mote controller at the
1) Erroneous address of unit to be coupled.
registration and
2) Slipping off of transmission line of unit to be coupled
access remote
controller
3) Faulty circuit board of unit to be coupled.
4) Installation miss of transmission line.
[Confirmation of different refrigerant system controller]
5) Breaking of power source of heat source unit to be
6) Slipping off of centralized control transmission line
7) Power supply connector (CN40) is not inserted into
8) More than 2 sets of power supply connector are
9) In the system connected with MELANS, power
10)Short circuit of centralized control transmission line.
Cause
(No connection).
confirmed.
(TB7) of heat source unit.
centralized control transmission line in grouping
with different refrigerant system without using
MELANS.
inserted into the centralized control transmission line
of heat source unit.
supply connector (CN40) is inserted into the
centralized control transmission line of heat source
unit.
Checking method & countermeasure
a) Confirm the address of unit to be
coupled.
b) Check the connection of transmission
line.
c) Check the transmission terminal block
voltage of unit to be coupled.
i) Normal if voltage is DC17 ~ 30V
ii) Check the item d) in case other than i).
d) Confirm the power source of heat source
unit to be coupled with the unit to be
confirmed.
e) Confirm that the centralized control
transmission line (TB7) of heat source
unit is not slipped off.
f) Confirm the voltage of centralized control
transmission line.
i) Normal in case of 10V ~ 30V
ii) Check the items 7) ~ 10) left in case
–86–
that other than i).