Mitsubishi Electric CITY MULTI PQRY-P200YMF-B Service Handbook page 123

Air conditioners city multi
Table of Contents

Advertisement

Checking code
Meaning, detecting method
4260
Cooling fan
If the heat sink temperature (THHS)
abnormality
60°C for 20 minutes or longer just
before the inverter starts.
5101
Discharge
<Other than THHS>
(TH1)
1 A short in the thermistor or an
open circuit was sensed. The
5102
Low
heat source unit switches to the
pressure
temporary stop mode with re-
saturation
starting after 3 minutes, then if
(TH2)
the temperature detected by the
thermistor just before restarting
5103
Accumulater
is in the normal range, restart-
liquid level
ing takes place.
2 If a short or open circuit in the
(TH3)
thermistor is detected just be-
5104
Accumulater
fore restarting, error code
liquid level
"5101", "5102", "5103", "5104",
(TH4)
"5106", "5108", "5109" or "5112"
is displayed.
5106
Water
3 In the 3 minute restart mode,
tempera-
the abnormal stop delay LED is
ture (TH6)
displayed.
4 The above short or open circuit
5107
(THINV)
is not detected for 10 minutes
after the compressor starts, or
5109
CS circuit
for 3 minutes during defrosting
(TH9)
or after recovery following de-
frosting.
5110
Radiator
<THHS>
panel
If a heat sink (THHS) temperature
(TH HS)
of
–40°C is detected just after
the inverter starts or during inverter
5112
Compres-
operation.
sor shell
tempera-
ture
(TH10)
5111
Liquid inlet
1. When short (high temp. inlet) or
(TH11)
open (low temperature inlet) of
thermistor is detected during
operation, error stop will be
commenced displaying "5111"
or "5112", "5113" or "5114", or
Bypass
"5115" or "5116.
outlet
2. The above detectection is not
(TH12)
made during defrostig and 3-
minute after changing operation
mode.
Bypass
inlet
(TH15)
Intermedi-
ate section
(TH16)
Cause
1) Same as "4230."
1) Thermistor
2) Lead wires are being pinched.
3) Insulation is torn.
4) A connector pin is missing, or there
is faulty contact.
5) A wire is disconnected.
6) The thermistor input circuit on the
MAIN circuit board is faulty.
(In the case of the THHS, replace
the INV board.)
Short Circuit Detection
TH1
240°C or higher (0.57 kΩ)
TH2
70°C or higher (1.71 kΩ)
TH3
70°C or higher (1.14 kΩ)
TH4
70°C or higher (1.14 kΩ)
TH6
110°C or higher (0.4 kΩ)
TH9
70°C or higher (1.14 kΩ)
THHS 100°C or higher (1.14 kΩ)
TH10
240°C or higher (0.57 kΩ)
THINV 100°C or higher (0.57 kΩ)
1) Thermistor trouble.
2) Biting of lead wire.
3) Broken cover.
4) Coming off of pin at connector por-
tion, poor contact.
5) Broken wire.
6) Faulty thermistor input circuit of
control board.
Short Detected
TH11
110°C or more (0.4 kΩ)
TH12
110°C or more (0.4 kΩ)
TH15
70°C or more (1.14 kΩ)
TH16
70°C or more (0.4 kΩ)
–120–
Checking method & Countermeasure
Same as "4230."
Check the thermistor's resistance.
Check if the lead wires are pinched.
Check for tearing of the insulation.
Check if a pin is missing on the con-
nector.
Check if a wire is disconnected.
Check the temperature picked up by
the sensor using the LED monitor.
If the deviation from the actual tem-
perature is great, replace the MAIN cir-
cuit board.
(In the case of the THHS, replace the
INV board.)
Open Circuit Detection
15°C or lower (321 kΩ)
–40°C or lower (130 kΩ)
–40°C or lower (130 kΩ)
–40°C or lower (130 kΩ)
–40°C or lower (130 kΩ)
–40°C or lower (130 kΩ)
–20°C or lower (2.5 MΩ)
–15°C or lower (1656 kΩ)
–20°C or lower (1656 kΩ)
Check thermistor resistance.
Check lead wire biting.
Check broken cover.
Check coming off of pin at connector.
Check broken wire.
Check sensor sensing temperature. If
it deviates from the actual temerature
seriously, replace control panel.
Open Detected
–40°C or less (130 kΩ)
–40°C or less (130 kΩ)
–40°C or less (130 kΩ)
–40°C or less (130 kΩ)