Mitsubishi Electric CITY MULTI PQRY-P200YMF-B Service Handbook page 121

Air conditioners city multi
Table of Contents

Advertisement

Checking code
Meaning, detecting method
4210
Breaking of
1. If IDC
overcurrent
during inverter operation.
2. If the voltage of the INV board's
sensor circuit input is what it
should not normally be.
4220
Bus voltage
1. If VDC
abnormality
ing inverter operation.
2. If VDC
ing inverter operation.
103 A peak is detected
1) The power supply voltage is abnor-
mal.
2) The wiring is defective.
3) The inverter/compressor is defec-
tive.
400 V is detected dur-
1) The power supply voltage is abnor-
mal.
800 V is detected dur-
2) The wiring is defective.
3) The rush current prevention resis-
tors (R1, 5) are defective.
4) The electromagnetic contactor
(52C) is defective.
5) The diode stack (DS) is defective.
6) The reactor (DCL) is defective.
7) The inverter output is grounded.
8) The circuit board is defective.
Cause
–118–
Checking method & Countermeasure
Check if an instantaneous power
failure or power failure, etc. has oc-
curred.
Check if the voltage is the rated volt-
age value.
Check 1, the connections, 2, contact
at the connectors, 3 tightening torque
at screw tightened portions, 4, wiring
polarities, 5, for broken wires, and 6,
for grounding in the following wiring.
TB1A~DS~[52C, R1, R5]~[C2,
C3]~TRM Wiring
TRM~CNVDC Wiring
TRM~Compressor Wiring
[CN2-1, CN2-2, CN2-3, CN3]~TRM
Wiring
*
Check if the wiring polarities are as
shown on the wiring diagram plate.
*
Check the coil resistances and in-
sulation resistance of the compres-
sor.
Go to "Treatment of Inverter/Compres-
sor Related Trouble."
Check if an instantaneous stop or
power failure, etc. has occurred.
Check if the voltage is the rated volt-
age value.
Check 1, the connections, 2, contact
at the connectors, 3 tightening torque
at screw tightened portions, 4, wiring
polarities, 5, for broken wires, and 6,
for grounding in the following wiring.
TB1A~DS~[52C, R1, R5]~[C2,
C3]~TRM Wiring
TRM~CNVDC Wiring
*
Check if the wiring polarities are as
shown on the wiring diagram plate.
To judge failure of R1 and R5, go to
"Individual Parts Failure Judgment
Methods."
To judge failure of the 52 C, go to "In-
dividual Parts Failure Judgment Meth-
ods."
To judge failure of the DS, go to "Indi-
vidual Parts Failure Judgment Meth-
ods."
To judge failure of the DCL, go to "In-
dividual Parts Failure Judgment Meth-
ods."
Check the wiring between the TRM
and the compressor.
Check the compressor's insulation
resistance.
If none of the items in 1) to 7) is appli-
cable, and if the trouble reappears even
after the power is switched on again,
replace the INV board (when replacing
the circuit board, be sure to connect all
the connectors, ground wires, etc. se-
curely).