Mitsubishi Electric CITY MULTI PQRY-P200YMF-B Service Handbook page 108

Air conditioners city multi
Table of Contents

Advertisement

(3) Thermistor (Liquid and gas piping temperature detection)
Procedure
1. Remove the service panel
1 Use the procedure under (1)-1.2 to check TH11,
TH12, and TH15.
2. Disconnect the piping sensor lead from the control-
ler panel.
1 TH11 - TH12 (CN10)
2 TH15, TH16 (CN11)
3. Pull the temperature sensor from the temperature
sensor housing and replace it with a new sensor.
4. Connect the temperature sensor lead securely to
the controller board.
(4) Pressure sensor
Procedure
1. Remove the sensor panel.
1 Use the procedure under (1)-1.2 to check PS1
and PS3.
2. Disconnect the connector of the applicable pressure
sensor from the controller board and insulate the
connector.
1 Liquid pressure sensor (CNP1)
2 Intermediate pressure sensor (CNP3)
3. Install a new pressure sensor at the location shown
in the photograph, and plug the connector into the
controller board.
Important
1 In the case of gas leakage from the pressure sen-
sor, take actions to fix the leak before performing
the above procedure.
Be careful when removing heavy parts.
TH15 TH11 TH12
TH16
PS1
PS3
–105–