AIR CONDITIONERS MODEL PQHY-P Y(S)HM-A PQRY-P Y(S)HM-A - For ground source application DATA BOOK...
Page 2
MULTI air conditioning system and/or to prepare documents for promotions. Along with the DATABOOK, MITSUBISHI ELECTRIC provides a Design-Tool software to ensure the users to design the system correctly and simplify the calculations. Please contact your local distributor for this software.
Contents I Brine information 1. Brine freezing temperature ......................1 2. Capacity correction by brine concentration (For heat source unit) ........2 3. Pressure drop correction by brine concentration (For heat source unit) ......3 II Heat source unit information 1.
Page 4
3. PQRY-P-Y(S)HM-A ........................63 (1)Specification ............................63 (1)-1 Heat source units specification for standard combination (Standard CITY MULTI indoor units, PWFY-P100VM-E-BU, PWFY-P100/200VM-E-AU) ..63 (2)External dimension ..........................71 (3)Center of gravity ............................73 (4)Electrical wiring diagram .......................... 74 (5)Sound levels ............................75 (6)Capacity tables with indoor units ......................
Brine information 1.Brine freezing temperature Brine concentration is decided by the freezing temperature. First, it is necessary to decide the freezing temperature and find out brine concentration which will correspond to the freezing temperature. Propylene Glycol Propylene Glycol Ethylene Glycol Ethylene Glycol Brine concentration [wt%] Note;...
2.Capacity correction by brine concentration (For heat source unit) Depending on the freezing temperature and brine concentration, the ratio of unit capacity will change. As shown in the line diagram, higher the brine concentration, the lower the ratio of capacity becomes. Cooling PQHY PQRY...
3.Pressure drop correction by brine concentration (For heat source unit) Also, water pump is selected by the ratio of pressure drop of depending on the brine concentration. Cooling Inlet-water temp. [°C] Ethylene Glycol (cooling) Ethylene Glycol (cooling) -5°C 0°C 5°C 10°C 100% Brine concentration [wt%]...
Heat source unit information 1.General lineup of water-cooled heat source unit WY (Heat Pump) Series (8HP-36HP) PQHY-P YHM-A PQHY-P YSHM-A Model 10HP 12HP 16HP Model Name PQHY-P200YHM-A PQHY-P250YHM-A PQHY-P300YHM-A PQHY-P400YSHM-A Model 18HP 20HP 22HP 24HP Model Name PQHY-P450YSHM-A PQHY-P500YSHM-A PQHY-P550YSHM-A...
(1)-2 System specification for closed control system (PFD-P250/500VM-E) Model Name Indoor PFD-P250VM-E Heat source PQHY-P250YHM-A(For Ground source) Cooling Heating System capacity 28.0 31.5 System Power input 7.95 8.01 System current 14.5 / 13.7 / 13.3 14.6 / 13.8 / 13.4 Power source 3N ~ 380 / 400 / 415 V(50Hz), 400 / 415 V(60Hz) Power input...
Page 24
Model Name Indoor PFD-P500VM-E Heat source PQHY-P250YHM-A(For Ground source)×2 Cooling Heating System capacity 56.0 63.0 System Power input 15.9 16.02 System current 27.9 / 26.4 / 25.5 28.1 / 26.6 / 25.7 Power source 3N ~ 380 / 400 / 415 V(50Hz), 400 / 415 V(60Hz) Power input Current 9.5 / 9.0 / 8.7...
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low noise mode automatically in the case that the operation condition is severe. Sound level of PQHY-P200YHM-A Stand 50/60Hz Stand 50/60Hz...
Page 31
Sound level of PQHY-P500YSHM-A Measurement condition PQHY-P400,450,500,550,600YSHM-A Stand 50/60Hz 50/60Hz NC-70 NC-60 NC-50 NC-40 Measurement location NC-30 Approximate minimum audible limit on NC-20 continuous noise Octave band central frequency (Hz) dB(A) Standard 50/60Hz 64.0 57.0 51.0 46.5 45.0 42.0 46.0 35.5 52.0 Low noise mode 50/60Hz...
Page 32
Sound level of PQHY-P750YSHM-A Measurement condition PQHY-P650, 700, 750, 800, 850YSHM-A Stand 50/60Hz 50/60Hz NC-70 NC-60 NC-50 NC-40 Measurement location NC-30 Approximate minimum audible limit on NC-20 continuous noise Octave band central frequency (Hz) dB(A) Standard 50/60Hz 65.5 58.5 52.5 48.0 47.0 44.0 47.5 37.0 54.0...
Page 33
Measurement condition PQHY-P900YSHM-A Measurement location Sound level of PQHY-P900YSHM-A Stand 50/60Hz 50/60Hz NC-70 NC-60 NC-50 NC-40 NC-30 Approximate minimum audible limit on NC-20 continuous noise Octave band central frequency (Hz) dB(A) Standard 50/60Hz 70.0 60.5 54.0 49.0 43.5 44.5 48.5 41.5 55.0 Low noise mode 50/60Hz 64.5 58.0 52.0 48.0 43.5 42.0...
Correction by refrigerant piping length Cooling PQHY-P450YSHM-A PQHY-P200YHM-A Total capacity of indoor unit Total capacity of indoor unit 1.00 1.00 0.95 0.95 0.90 0.90 0.85 0.85 0.80 0.80 0.75 0.75 0.70 0.70 0.65 0.65 Piping equivalent length (m) Piping equivalent length (m)
Page 51
PQHY-P850YSHM-A PQHY-P650YSHM-A Total capacity of indoor unit Total capacity of indoor unit 1.00 1.00 0.95 0.95 0.90 0.90 0.85 0.85 0.80 0.80 0.75 0.75 1105 0.70 0.70 0.65 0.65 Piping equivalent length (m) Piping equivalent length (m) PQHY-P700, 750YSHM-A PQHY-P900YSHM-A Total capacity of indoor unit Total capacity of indoor unit 1.00...
Correction by water temperature (For heat source unit) (9)-1 Connection with standard CITY MULTI indoor units Cooling Heating Capacity Capacity Input Input Heat source unit (WY) inlet-water temp. [°C] Heat source unit (WY) inlet-water temp. [°C] (9)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit) Cooling HEX unit HEX unit...
(10) Correction by water flow rate (For heat source unit) (10)-1 Connection with standard CITY MULTI indoor units Cooling Heating Capacity Capacity Input Input *The drawing indicates characteristic per unit. *The drawing indicates characteristic per unit. 1.05 1.05 0.95 0.95 Heat source unit (WY) water-volume [m /h(/unit)] Heat source unit (WY) water-volume [m /h(/unit)]...
(11) Correction by indoor temperature (11)-1 Connection with standard CITY MULTI indoor units Cooling Heating Capacity Capacity Intake air temp. Intake air temp. Input Input 15 16 17 18 19 20 21 22 23 24 25 26 Intake air temp. (Room temp.) [°CWB] Intake air temp.
(13) Water pressure drop correction by water volume (13)-1 Heat source unit correction (Connection with Standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU, PFD-P250/500VM-E) Heat source unit inlet-water volume [m /h(/unit)] Note: The drawing indicates characteristic per unit. When using brine, refer to “3.Pressure drop correction by brine concen- tration”...
(14) Operation temperature range (14)-1 Connection with standard CITY MULTI indoor units Cooling °FWB°CWB -20 -15 -10 °C 95 104 113 122 °F Heat source unit (WY) circulating water temperature Heating °FDB°CDB -20 -15 -10 °C 95 104 113 122 °F Heat source unit (WY) circulating water temperature (14)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit)
(14)-3 Connection with PFD-P250/500VM-E Cooling °FDB°CDB 41 5 °C 122 °F Heat source unit (WY) circulating water temperature Heating °FDB°CDB 41 5 °C 122 °F Heat source unit (WY) circulating water temperature - 56 -...
The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as T a ble 15-1, or You shall follow the local industrial standard.
Item Piping in the figure Max. length Max. equivalent length Heat source Model M (m/bent [ft./bent]) Total piping length A+B+C+D+E+a+b+c+d+e+f+g 300 [984'] PQHY-P200YHM-A 0.35 [1.15] Farthest IU from HU (L1) A+C+D+E+g / A+B+c 165 [541'] 190 [623'] PQHY-P250YHM-A 0.42 [1.38]...
(15)-3 PQHY-P400-600YSHM Piping (Connection with standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU) Note1. No Joint after Header; Piping direct to Indoor Unit from Header; Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better; Piping length needs to consider the actual length and equivalent length which bents are counted. Equivalent piping length (m)=Actual piping length+"M"...
(15)-4 PQHY-P650-900YSHM Piping (Connection with standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU) Note1. No Joint after Header; Piping direct to Indoor Unit from Header; Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better; Piping length needs to consider the actual length and equivalent length which bents are counted. Equivalent piping length (m)=Actual piping length+"M"...
(15)-5 PQHY-P250/P250+P250YHM (Connection with PFD indoor unit) Fig.15-5A : Connection with PFD-P250VM-E Fig.15-5AA : Connection with PFD-P500VM-E (two refrigerant circuit system) IU : Indoor unit , HU : Heat source unit Table : 15-5-1. Piping length Item Piping in the figure Max.
L/min Pressure drop kPa 4.5 ~ 7.2 Operating volume range Type x Quantity Compressor Inverter scroll hermetic compressor Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output Case heater 0.035(240 V) Lubricant MEL32 External finish Acrylic painted steel plate...
Page 68
Water flow rate m water L/min Pressure drop kPa 4.5 ~ 7.2 Operating volume range Type x Quantity Inverter scroll hermetic compressor Compressor AC&R Works, MITSUBISHI ELECTRIC CORPORATION Manufacture Starting method Inverter Motor output 0.035(240 V) Case heater MEL32 Lubricant...
Page 69
L/min Pressure drop kPa 4.5 ~ 7.2 Operating volume range Type x Quantity Compressor Inverter scroll hermetic compressor Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Motor output 0.035(240 V) Case heater MEL32 Lubricant External finish Acrylic painted steel plate...
Page 70
4.5 + 4.5 ~ 7.2 + 7.2 Operating volume range Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Lubricant Acrylic painted steel plate...
Page 71
4.5 + 4.5 ~ 7.2 + 7.2 Operating volume range Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION Starting method Inverter Inverter Lubricant External finish...
(10) Correction by water temperature (For heat source unit) (10)-1 Connection with standard CITY MULTI indoor units Cooling Heating Capacity Capacity Input Input Heat source unit (WR2) inlet-water temp. [°C] Heat source unit (WR2) inlet-water temp. [°C] (10)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit) Cooling HEX unit HEX unit...
(11) Correction by water flow rate (For heat source unit) (11)-1 Connection with standard CITY MULTI indoor units Cooling Heating Capacity Capacity Input Input *The drawing indicates characteristic per unit. *The drawing indicates characteristic per unit. 1.05 1.05 0.95 0.95 Heat source unit (WR2) water-volume [m /h(/unit)] Heat source unit (WR2) water-volume [m /h(/unit)]...
(12) Correction by indoor temperature (12)-1 Connection with standard CITY MULTI indoor units Cooling Heating Capacity Capacity Intake air temp. Intake air temp. Input Input 15 16 17 18 19 20 21 22 23 24 25 26 Intake air temp. (Room temp.) [°CWB] Intake air temp.
(14) Water pressure drop correction by water volume (14)-1 Heat source unit correction (Connection with Standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU, PWFY-P100VM-E-BU) Heat source unit inlet-water volume [m /h(/unit)] Note: The drawing indicates characteristic per unit. When using brine, refer to “3.Pressure drop correction by brine concen- tration”...
(15) Operation temperature range (15)-1 Connection with standard CITY MULTI indoor units Cooling °FWB°CWB -20 -15 -10 °C 95 104 113 122 °F Heat source unit (WR2) circulating water temperature Heating °FDB°CDB -20 -15 -10 °C 95 104 113 122 °F Heat source unit (WR2) circulating water temperature Combination of cooling/heating operation (Cooling main or Heating main)
(15)-3 Connection with PWFY-P100/200VM-E-AU (HEX unit) Cooling °F °C °C 95 104 113 122 °F Heat source unit (WR2) circulating water temperature Heating °F °C °C °F 95 104 113 122 Heat source unit (WR2) circulating water temperature - 103 -...
The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as T a ble 16-1, or You shall follow the local industrial standard.
(16)-2 PQRY-P200-300YHM Piping IF 16 ports or less are in use, i.e., if only one BC controller is in use with no sub BC controller (Connection with standard CITY MULTI indoor units, PWFY-P100VM-E-BU, PWFY-P100/200VM-E-AU) Note1. No Header usable on PQRY system. Note2.
(16)-3 PQRY-P200-300YHM Piping IF more than 16 ports are in use, or if there is more than one BC controller in use for one Heat source unit (Connection with standard CITY MULTI indoor units, PWFY-P100VM-E-BU, PWFY-P100/200VM-E-AU) Note1. No Header usable on PQRY system. Note2.
(16)-4 PQRY-P400YHM Piping IF more than 16 ports are in use, or if there is more than one BC controller in use for two heat source units (Connection with standard CITY MULTI indoor units, PWFY-P100VM-E-BU, PWFY-P100/200VM-E-AU) Note1. No Header usable on PQRY system. Note2.
(16)-5 Total piping length restrictions [PQRY-P200, 250, 300YHM-A(-BS)(-H)] [PQRY-P400, 450, 500, 550, 600YSHM-A(-BS)(-H)] 1000 1000 90 100 110 90 100 110 Distance between heat source unit and BC controller(m) Distance between heat source unit and BC controller(m) - 108 -...
(16)-6 Refrigerant charging calculation Sample connection (with 3 BC controller and 6 indoor units) (Main unit) (Sub unit) Heat source unit Twinning kit (High/Low press.) CMY-Q100VBK: The Low press. kit is set in the Main unit ; The High press. kit is to be installed in the field. CMY-Y202-G2 5 : P140 CMY-Y102L-G2...
Page 114
DATA BOOK PQHY-P Y(S)HM-A PQRY-P Y(S)HM-A - For ground source application HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN http://Global.MitsubishiElectric.com New publication effective Sep.2010 Specifications subject to change without notice MEE09K040...
Page 115
Related Links Model Number: CMB-P1016V-GA PQRY-YGM-A_Databook CMB-P104-1016V-G_Declaration_of_Conformity_(EU-04002D) CMB-P104-1016V-G_Installation_Manual_(WT04305X01) CMB-P104-1016V-G_Parts_Catalog_(BWE04140B) PQRY-P-YHM-A_Ground_Source_Databook PQRY-P200-250YGM-A_Service_Manual_(HWE05030) PQRY-YHM-A_Databook PURY-EP-YHM-A_Databook PURY-EP200-600YHM_Service_Manual_(HWE0713A) PURY-P200-650YGM-A_Service_Manual_(HWE04020) PURY-YGM-A_Databook PURY-YHM-A_Databook...