Goodman ComfortNet ACVC9 Technical Manu Technical Manualal page 18

90% up to 96% gas furnace units
Hide thumbs Also See for ComfortNet ACVC9:
Table of Contents

Advertisement

BLOWER PERFORMANCE SPECIFICATIONS
*MVC951155DX Cooling/Heating Speed Charts
*MVC951155DX
Cooling Speed
( @ .1" - .8" w.c. ESP)
Tap
Adjust
Minus 10%
Minus 5%
A
Normal
Plus 5%
Plus 10%
Minus 10%
Minus 5%
B
Normal
Plus 5%
Plus 10%
Minus 10%
Minus 5%
C
Normal
Plus 5%
Plus 10%
Minus 10%
Minus 5%
D
Normal
Plus 5%
Plus 10%
1.
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
2.
For most jobs, about 400 CFM per ton when cooling is desirable.
3.
Do not operate above .5" w.c. ESP in heating mode. Operating CFM between .5" and .8" w.c. is tabulated for cooling purposes only.
4.
Continuous fan speeds of 25%, 50%, 75% of maximum cooling airflow are available when using a communicating thermostat and 25%, 50%, 75%, 100%
of maximum cooling airflow are available in legacy mode by setting dip switches
18
High-Stage
Low-Stage
CFM
CFM
720
468
760
494
800
520
840
546
880
572
990
644
1,045
679
1,100
715
1,155
751
1,210
787
1,260
819
1,330
865
1,400
910
1,470
956
1,540
1,001
1,620
1,053
1,710
1,112
1,800
1,170
1,890
1,229
1,980
1,287
*MVC951155DX
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 35 - 65°F)
High-Stage
Tap
Adjust
CFM
Minus 10%
1,594
Minus 5%
1,682
A
Normal
1,771
Plus 5%
1,860
Plus 10%
1,948
Minus 10%
1,640
Minus 5%
1,731
B
Normal
1,822
Plus 5%
1,913
Plus 10%
2,004
Minus 10%
1,685
Minus 5%
1,778
C
Normal
1,872
Plus 5%
1,966
Plus 10%
2,059
Minus 10%
1,730
Minus 5%
1,826
D
Normal
1,922
Plus 5%
2,018
Plus 10%
2,114
Low-Stage
Rise
CFM
(°F)
1,107
63
1,169
60
1,230
57
1,292
54
1,353
52
1,139
62
1,202
59
1,265
56
1,328
53
1,392
50
1,170
60
1,235
57
1,300
54
1,365
51
1,430
49
1,202
58
1,268
55
1,335
53
1,402
50
1,469
48

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents