General" Group - Viessmann Vitotronic 300 GW6B Installation Instructions Manual

Weather-compensated boiler and heating circuit control unit in single boiler or multi boiler systems
Table of Contents

Advertisement

Vitotronic 300, GW6B Installation and Service

"General" Group

Coding in the factory set condition
System design
00:1
System version 1:
One heating circuit without mixing valve
A1 (heating circuit 1), without DHW
heating
Value address
Description
00: ...
2
One heating circuit without mixing valve A1 (heating circuit 1), with DHW heating;
recognized automatically.
3
One heating circuit with mixing valve M2 (heating circuit 2), without DHW heating.
4
One heating circuit with mixing valve (heating circuit 2), with DHW heating.
5
One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
M2 (heating circuit 2), without DHW heating; recognized automatically.
6
One heating circuit without mixing valve A1 (heating circuit 1), one heating circuit with mixing valve
M2 (heating circuit 2), with DHW heating; recognized automatically.
7
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3),
without DHW heating.
8
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW
heating.
9
One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
valve M2 (heating circuit 2) and M3 (heating circuit 3), without DHW heating; recognized
automatically.
10
One heating circuit without mixing valve A1 (heating circuit 1), two heating circuits with mixing
valve M2 (heating circuit 2) and M3 (heating circuit 3), with DHW heating; recognized automatically.
Coding in the factory set condition
"With EA1 extension: DHW recirculation pump runtime for brief operation"
12:5
DHW recirculation pump runtime for
brief operation: 5 min
"With EA1 extension: Temperature demand"
1e:0
Analogue input 0-10 V:
Temperature demand from 32 to 212°F
(0 to 100°C):
1 V
50°F (10°C)
10 V
"Reset time hydraulic switch/buffer
20:...
Controller integral time for low loss
header in sec, factory set condition
defaulted by the boiler coding card.
The greater the integral action time,
the more accurate but slower the
controller.
"Controller delay hydraulic switch/buffer
22:...
Controller delay low loss header in
minutes, time between burner start and
controller start.
2f:0
Do not adjust!
"AM1 extension"
32:0
Without AM1 extension
"Function output A2 at AM1 extension"
33:1
Heating circuit pump, heating circuit
without mixing valve A1
(heating circuit 1)
212°F (100°C)
Possible change
00:2
For system schemes,
to
see the following table:
00:10
Possible change
12:1
Adjustable from 1 to 60 min
to
12:60
1E:1
Adjustable from 86 to 248°F
(30 to 120°C):
1 V
86°F (30°C)
10 V
20:1
Adjustable from 10 to 1990 sec,
to
1 step
20:199
20:1
Adjustable from 1 to 199 min
to
20:199
--
--
32:1
With AM1 extension
33:0
DHW recirculation pump
33:2
DHW loading pump
Coding level 2
248°F (120°C)
10 sec
95