Connecting Pumps - Viessmann Vitotronic 300 GW6B Installation Instructions Manual

Weather-compensated boiler and heating circuit control unit in single boiler or multi boiler systems
Table of Contents

Advertisement

Vitotronic 300, GW6B Installation and Service

Connecting Pumps

Legend
A Pumps
B To the control unit
Rated voltage
Rated current Max.
Note: Maximum output 6FLA shared between all
120V outputs.
Pumps 120V
Available pump connections
sÖM1/A1 Heating circuit 1 pump
sÖM2
Heating circuit 2 pump
sÖM3
Heating circuit 3 pump
DHW pump
sA
sK
DHW recirculation pump
sL
Boiler pump
120V~
2A~
Available connections
Connections on extension for heating circuit with mixing
valve HC2/M2, HC3/M3
Plug
Terminal
5
L, N, G
sÖ M2
6
L, N, G
sÖ M3
Connections on the PCB 120V~
9
L, N, G
sÖA1
8
L, N, G
sA
7
L, N, G
sK
10
L, N, G
sL
Electrical Connections
Component
Heating circuit pump
Heating circuit pump
Heating circuit pump
for heating circuit A1
or
Primary pump,
primary store system
DHW pump
DHW recirculation
pump
boiler pump, system
pump
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300Gw6b

Table of Contents