Discharge Testing - Hammerhead Charger 48V Operator's Manual

Electric vehicle
Table of Contents

Advertisement

TROJAN BATTERY USER'S GUIDE

Discharge Testing

7.5.
Connect and start discharger
Record the runtime (minutes) when discharge is complete
Correct runtime minutes for temperature using the following formula (valid between
24°C (75°F) and 32°C (90°F):
o Mc = Mr [1 – 0.009 (T - 27)] where Mc is the corrected minutes, Mr is the
minutes recorded and T is the temperature at the end of discharge in °C
If the discharge time is greater than 50% of the batteries' rated capacity then all the
batteries are operational
Reconnect the discharger to record the individual battery voltage while still under
load (current being drawn)
If the discharge runtime is less than 50% of the batteries' rated capacity, the
batteries with a voltage that is 0.5V lower than the highest voltage may be a failed
battery
There are other methods of testing batteries including internal resistance (i.e. CCA testers)
and carbon-pile discharge testers. However these are not suitable testing methods for deep
cycle batteries.