5.4 Boiler Venting – Side-wall or Direct Vent Systems Sizing Tables & Vent Safety Device
All venting lengths must be calculated to equivalent lengths,
all application must include at least one 90° elbow
Venting must be a type 'BH" [AL294C® material]
Maximum vent length [equivalent] = 30 ft. [9m]
Minimum vent length [equivalent] 5 ft. [1.5m]
Maximum number of 90° elbows = 2 or 3 45° elbows, each
90° e bow is equivalent to 10 ft. or straight pipe, the 45°
elbow is equivalent = 5 ft.
Condensate TEE must be provided [equivalent length = 7 ft.]
Appliance reducing adapter [equivalent length 3 ft.]
Sealed combustion, combustion air intake sizing, must be
sized according to the burner manufacturers instructions
Vent [breeching] pressure shall not exceed 0.20 inches w.c.
[0.50 mbar]
Venting
Determining vent length [equivalent] Example:
Appliance reducing adapter
Condensate TEE
12" vent straight vent pipe
E bow 90°
Termination TEE
Length [equivalent] =
GT 210 A Series
Boiler
Model
Connection
ø
GT 214 A
6 inch
GT 215 A
6 inch
GT 216 A
7 inch
GT 217 A
7 inch
GT 218 A
7 inch
Vent termination must be a TEE type, follow warning
regarding
termination
termination TEE length in the vent length calculation.
Venting shall be sloped, so any condensation developed will
drain through the condensate TEE fitting
Vent safety device, differential air pressure switch [manual
reset] NC switch opens on rise of pressure.
Optional function of power burners which can employ an
post purge function to exhaust flue gases for a fixed time [1
minute to 4 minutes maximum]
Burner employing a standby air damper closed position, the
closed position should be slightly opened to allow hot flue
gases to escape upward through venting and not be
entrapped in the combustion head. Important note, that in
negative building pressures, the observation and odor of flue
gases may enter the boiler room.
[x1] = 3 ft.
[x1] = 7 ft.
[x3] = 3 ft.
[x1] = 10 ft.
[x1] = 0 ft.
23 ft.
Oil-Gas
[∆p] Pressure switch
Vent ø
Setting [inches w.c.]
4 inch
Set Switch @ 150%
4 inch
above gas burner gas
5 inch
manifold or oil burner
5 inch
head pressure
5 inch
locations.
Do
not
include
31
the